3-38
Programming and Parameters
D
YNAMIC C
O
NTR
O
L
Re
sta
rt
Mo
des
175 [Auto Rstrt Delay]
Sets the time between restart attempts
when [Auto Rstrt Tries] is set to a value
other than zero.
Default:
Min/Max:
Units:
30.0 Secs
0.5/30.0 Secs
0.1 Secs
178 [Sleep Wake Mode]
Enables/disables the Sleep/Wake
function. Important: When enabled, the
following conditions must be met:
•
A proper value must be programmed
for [Sleep Level] & [Wake Level].
•
A speed reference must be selected in
[Speed Ref A Sel].
•
At least one of the following must be
programmed (and input closed) in
[Digital Inx Sel]; “Enable,” “Stop=CF,”
“Run,” “Run Forward,” “Run Reverse.”
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Direct”
F
ile
Gr
oup
No
.
Parameter Name and Description
See
page 3-2
for symbol descriptions
Values
Re
lated
ATTENTION: Enabling the Sleep-Wake function can cause
unexpected machine operation during the Wake mode. Equipment
damage and/or personal injury can result if this parameter is used in
an inappropriate application. Do Not use this function without
considering the information below. Failure to observe this precaution
could result in personal injury or damage to equipment.
!
Conditions Required to Start Drive
Important: P089 [Logic Source Sel] = 0 “Terminal Blk”
Input
After Power-Up
After a Drive Fault
After a Stop Command
Reset by Stop-CF,
OIM or TB
Reset by Clear
Faults (TB)
OIM or TB
Stop
Stop Closed
Wake Signal
Stop Closed
Wake Signal
New Start or Run Cmd.
Stop Closed
Wake Signal
Stop Closed
Direct Mode
Analog Sig. > Wake Level
Enable
Enable Closed
Wake Signal
Enable Closed
Wake Signal
New Start or Run Cmd.
Enable Closed
Wake Signal
Enable Closed
Direct Mode
Analog Sig. > Wake Level
Run
Run For.
Run Rev.
Run Closed
Wake Signal
New Run Cmd.
Wake Signal
Run Closed
Wake Signal
New Run Cmd.
Wake Signal
Summary of Contents for 9VT201-007HTNNN
Page 1: ...VTAC 9 AC Drive Firmware Version 3 xx User Manual ...
Page 4: ...soc 2 ...
Page 14: ...P 8 Overview Publication 9VT UM001D EN P Notes ...
Page 56: ...1 42 Installation Wiring Publication 9VT UM001D EN P Notes ...
Page 62: ...2 6 Start Up Publication 9VT UM001D EN P Notes ...
Page 130: ...3 68 Programming and Parameters Publication 9VT UM001D EN P Notes ...
Page 150: ...4 20 Troubleshooting Publication 9VT UM001D EN P Notes ...
Page 176: ...A 26 Supplemental Drive Information Publication 9VT UM001D EN P Notes ...
Page 196: ...B 20 Using the LCD OIM Publication 9VT UM001D EN P Notes ...
Page 212: ...C 16 Application Notes Publication 9VT UM001D EN P Notes ...
Page 223: ......