QSHT 5700 Inverter Safe Torque-off Function
Hardwired Safe Torque-off
QuickStick HT User Manual
271
Rockwell Automation Publication MMI-UM007F-EN-P - September 2020
Figure 7-1: Normal System Operation
Table 7-3: Normal System Operation (legend)
Event
Description
1
At least one input is switched OFF. The GuardStopRequestStatus bit is set to 1.
2
Second input is switched OFF within 1 second of event 1. This event must always occur
within 1 second to prevent a GuardStopInputFault condition. For more information see
QSHT 5700 Inverter Fault Troubleshooting
3
First input is switched ON.
4
Second input is switched ON within 1 second of event 3.
5
Both inputs are in the ON state simultaneously within 1 second. As a result, Guard-
StopInputFault is not posted.
6
The GuardStopRequestStatus bit sets back to 0 if event 4 occurs within a 100 ms inter-
val after event 3. If event 4 is outside of the 100 ms interval, but within the 1 second
interval after event 3, then the GuardStopRequestStatus bit sets back to 0 after the 1
second interval following event 3 (not immediately following event 4).
1
3 4
5 6
24V DC
24V DC
0V DC
0V DC
0
1
0
1
0
1
2
SS_IN_CH0
SS_IN_CH1
GuardStopInputFault
SafeTorqueOffFault
GuardStopRequestStatus
No Fault
1 Second Discrepancy Limit
1 Second Discrepancy Limit
Torque Permitted
Torque Disabled
No Fault
Event