LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table 7.3 – Analog Output Connections (Terminals 10 and 11)
Terminal #
Signal
10
Analog Meter Output
11
Regulator Common
Notes: The output of this terminal is either 0-10 VDC or 4-20 mA as determined by the
setting of jumper J17 on the Regulator board. The analog output must also be
programmed via parameter P.012 for an indication of speed and direction or percent
of torque.
Table 7.4 – Analog Speed/Torque Reference Connections (Terminals 12-15)
Terminal #
Signal
12
Isolated Reference Voltage
13
VDC Speed/Torque Reference
14
mA Speed/Torque Reference
15
Isolated Reference Common
Notes: The analog speed/torque (P.008/U.000) reference is /-10 VDC or
+/-20 mA, as determined by the setting of jumper J4 on the Regulator board. The
analog reference can be adjusted using parameters P.009, P.010, and P.011.
Summary of Contents for 41LR4060
Page 6: ...IV LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 8: ...VI LiquiFlo 2 0 AC Drive User Manual ...
Page 10: ...VIII LiquiFlo 2 0 AC Drive User Manual ...
Page 12: ...1 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 30: ...2 18 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 40: ...3 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 50: ...4 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 78: ...7 22 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 90: ...9 10 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 96: ...B 2 LiquiFlo AC Power Modules Hardware Reference Version 6 4 ...
Page 98: ...C 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 100: ...D 2 LiquiFlo 2 0 AC Drive User Manual ...
Page 102: ...E 2 LiquiFlo 1 5 AC Power Modules Hardware Reference Version 1 2 ...
Page 107: ......