![Rockwell Automation 2711PC- T6C20D User Manual Download Page 94](http://html1.mh-extra.com/html/rockwell-automation/2711pc-t6c20d/2711pc-t6c20d_user-manual_1475620094.webp)
94
Publication 2711PC-UM001A-EN-P - March 2009
Chapter 6
Terminal Connections
Ethernet Cable
For PanelView Plus Compact 1000 terminals use Belden 7921A
shielded Ethernet Category 5e cable according to TIA 568-B.1 and
RJ45 connector according to IEC 60603-7 for compliance with the
European Union 89/336/EEC EMC Directive.
The maximum cable length between the terminal’s Ethernet port and a
10/100 Base-T port on an Ethernet hub (without repeaters or fiber) is
100 m (328 ft).
Security Considerations
IGMP (Internet Group Management Protocol) is used for IPv4
multicast. A multicast is communication between a single sender and
multiple receivers on a network. IGMP is used to exchange
membership status data between IPv4 routers that support
multicasting and members of multicast groups. A router is an
intermediary device on a communication network that expedites
message delivery by finding the most efficient route for a message
packet within a network, or by routing packets from one subnetwork
to another. A sub-network is a separate part of an organization’s
network identified through IP addressing.
PanelView Plus terminals provide level 2 (full) support for IPv4
multicasting (IGMP version 2) as described in RFC 1112 and RFC 2236.
SNMP (Simple Network Management Protocol) is used for internal
network management and is not supported.
Ports 137 and 138 are normally open to support the NetBIOS protocol
used by Windows CE.NET similar to other Microsoft and IBM network
operating systems.
WARNING
Do not connect or disconnect any communication cable with
power applied to this device or any device on the network. An
electrical arc could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
Summary of Contents for 2711PC- T6C20D
Page 6: ...6 Publication 2711PC UM001A EN P March 2009 Table of Contents ...
Page 8: ...8 Publication 2711PC UM001A EN P March 2009 Preface ...
Page 30: ...30 Publication 2711PC UM001A EN P March 2009 Chapter 3 Connecting Power ...
Page 86: ...86 Publication 2711PC UM001A EN P March 2009 Chapter 5 Installing and Replacing Components ...
Page 120: ...120 Publication 2711PC UM001A EN P March 2009 Appendix A Specifications ...
Page 122: ...122 Publication 2711PC UM001A EN P March 2009 Appendix B USB Devices ...
Page 126: ...126 Publication 2711PC UM001A EN P March 2009 Appendix C Available Fonts ...
Page 129: ......
Page 130: ......
Page 131: ......