Battery Precautions

Replace the Battery

Follow these steps to replace the lithium battery in the logic module of PanelView Plus or 
PanelView Plus Compact terminals.

1.

Disconnect power from the terminal.

2.

Place the terminal, display side down, on a flat stable surface.

3.

Detach the communication module, if attached, from the logic module by removing 
the four screws.

4.

Loosen the six captive screws that attach the logic module to the display module.

5.

Carefully lift the logic module away from the terminal and turn over to expose the 
circuit board.

WARNING

When you connect or disconnect the battery an electrical arc can occur. This could cause 
an explosion in hazardous location installations. Be sure that power is removed and the 
area is nonhazardous before proceeding. 

For safety information on the handling of lithium batteries, including handling and 
disposal of leaking batteries, see Guidelines for Handling Lithium Batteries, publication 

AG 5-4

. Replace the battery only with the indicated catalog number.

Do not dispose of battery in a fire or incinerator. Dispose of used batteries in accordance 
with local regulations.

Store batteries in a cool, dry environment. We recommend 25 °C (77 °F) with 40…60% 
relative humidity. You may store batteries for up to 30 days between -45…85 °C 
(-49…185 °F), such as during transportation. To avoid possible leakage, do not store 
batteries above 60 °C (140 °F) for more than 30 days.

Logic Module

Communication Module

Screw

Captive 
Screw

Display Module

Summary of Contents for 2711PC-T10C4D1

Page 1: ...lView Plus CE 700 to 1500 display modules Factory assembled PanelView Plus Compact 1000 terminal For complete information on installing wiring and troubleshooting the terminals refer to the publicatio...

Page 2: ...d with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automa...

Page 3: ...ake caution in this regard This equipment is supplied as open type equipment It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be p...

Page 4: ...en operating in a 55 C 131 F maximum ambient temperature Do not install the terminals in environments where atmospheric gases have ignition temperatures less than 135 C 275 F WARNING Explosion Hazard...

Page 5: ...p rature ambiante maximale de 55 C N installez pas les terminaux dans des environnements contenant des gaz atmosph riques inflammables moins de 135 C AVERTISSEMENT DANGER D EXPLOSION La substitution d...

Page 6: ...ectrical Code article 500 Terminals Control Drawing Selected nonincendive field wiring apparatus must have nonincendive circuit parameters conforming with Table 2 Table 1 PanelView Plus USB Port Circu...

Page 7: ...accordance with 501 10 B 3 of the National Electrical Code NEC ANSI NFPA 70 or other local codes as applicable This associated nonincendive field wiring apparatus has not been evaluated for use in co...

Page 8: ...etic interference EMI Grounding minimizes noise from EMI and is a safety measure in electrical installations For more information on grounding recommendations refer to the National Electrical Code pub...

Page 9: ...ay module See the instructions shipped with the logic module About the PanelView Plus Compact 1000 Terminal The PanelView Plus Compact 1000 terminal has a fixed configuration It does not support commu...

Page 10: ...h lb in Install the Terminal Before installing the terminal in a panel review the following topics Mounting clearances Panel cutout dimensions Product dimensions Mounting Clearances Allow adequate cle...

Page 11: ...aling gasket is properly positioned on the terminal Terminal Type Height mm in Width mm in 700 Keypad or Keypad and Touch 167 6 57 264 10 39 700 Touch 154 6 08 220 8 67 1000 Keypad or Keypad and Touch...

Page 12: ...end strips before installing the terminal if you are using keypad legend strips on keypad terminals Be careful not to pinch the legend strip during installation 4 Place the terminal in the panel cutou...

Page 13: ...ge to the product Rockwell Automation assumes no responsibility for water or chemical damage to the product or other equipment within the enclosure because of improper installation Terminal Type Heigh...

Page 14: ...or the PanelView Plus and PanelView Plus Compact 1000 touch only terminals The other size terminals look similar Measurements are in mm in 1000 Terminal Dimensions Keypad or Keypad Touch Touch Screen...

Page 15: ...or ease of installation wiring and maintenance Series A to D DC logic modules use a 3 position terminal block Series E or later DC logic modules use a 2 position terminal block All logic modules with...

Page 16: ...ntegrated 24V DC power supply Both isolated and non isolated power supplies have these ratings 24V DC nominal 18 32V DC 70 W maximum 2 9 A at 24V DC The power supply is internally protected against re...

Page 17: ...t and not connected to earth ground Multiple AC Power Supplies to Power Multiple DC Terminals TIP To identify non isolated DC logic modules refer to the PanelView Plus Terminals user manual publicatio...

Page 18: ...r to the PanelView Plus Terminals User Manual publication 2711P UM001 TIP Isolated DC logic modules are identified by catalog number 2711P RPxDx ATTENTION Use an SELV or PELV supply as required by loc...

Page 19: ...for proper connections 3 Secure the earth ground wire to the earth ground terminal screw at the bottom of the display DC Power Supply Connections WARNING Explosion Hazard Do not disconnect equipment u...

Page 20: ...ations for AC Input Power Terminal Block Wire Type Dual wire Gauge 1 1 Two wire max per terminal Single wire Gauge Terminal Screw Torque Stranded or solid Cu 90 C 194 F 22 16 AWG 22 14 AWG 0 56 N m 5...

Page 21: ...functional earth ground screw on the back of the display to ground bus 5 Apply AC power to the terminal WARNING Explosion Hazard Do not connect or disconnect equipment while circuit is live unless are...

Page 22: ...ect or disconnect the battery an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed and the area is nonhazardous before proceeding...

Page 23: ...ttery 8 Insert the new battery 9 Reattach the logic module by aligning the two connectors on the bottom of the module with the connectors on the terminal 10 Push down on the logic module until it is f...

Page 24: ...ULT indicator red for hardware faults When the terminal starts the fault indicator should be off except for a few brief flashes and the comm indicator on If the indicators remain off the power supply...

Page 25: ...n mode on the terminal access Terminal Settings Display Screen Saver Indicator States If the Terminal Stops During Startup Fault Red Indicator Comm Green Indicator Description Blinking 1 1 Blinking re...

Page 26: ...tegrity of the battery hardware 2 5 Registry Search Locates and loads the most recent valid registry Multiple copies of the registry are maintained If power is lost during a registry update a valid re...

Page 27: ...odule 30 Watchdog Test Watchdog test failure Reload the firmware If error persists replace the logic module 31 Stuck Key Function key failure Check that nothing is pressed against a key Reset the term...

Page 28: ...t voltage DC 24V DC nom 18 32V DC Power consumption DC 70 W max 2 9 A 24V DC 39 W typical 1 6 A 24V DC Input voltage AC 85 264V AC 47 63 Hz Power consumption AC 160 VA max 65 VA typical PCI slot max a...

Page 29: ...at 25 C 77 F Clock Battery backed 2 minutes per month Status indicators COMM green Fault red Application flash memory 700 to 1500 series D or earlier logic modules 2711P RW1 2711P RW2 2711P RW3 700 t...

Page 30: ...missions CE LVD EN 61131 2 Programmable Controllers C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Marine Products identified with the suffix M in the ca...

Page 31: ...PanelView Plus 700 to 1500 and PanelView Plus Compact 1000 Terminals and Display Modules 31 Publication 2711P IN001I EN P November 2009...

Page 32: ...llation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running New Product Satisfa...

Reviews: