Rockwell Automation Publication 750-TG101A-EN-P - June 2022
161
Chapter 6 Frame 7 Renewal Kits Installation
AC Precharge Circuit Board
(400/480V) Replacement
Replacement kit catalog number: SK-RT-ACPC-CDF7
Remove the AC Precharge Circuit Board (400/480V)
Follow these steps to remove the AC precharge circuit board.
1. Review the
.
2. Turn off and lock-out incoming power. See
.
3. Access the drive interior:
• For IP00, NEMA/UL Open Type, IP21, NEMA/UL Type 1 and flange,
NEMA/UL Type 4X/12 back enclosures, remove the cover. See
• For IP54, NEMA/UL Type 12 enclosures, open the enclosure and
remove the protective guard. See
Remove the Protective Guard (IP54,
NEMA/UL Type 12 Enclosure) on page 129
.
4. Remove these connections from the control pod:
a. If used, disconnect the HIM DPI cable from the connector (port 2) on
the HIM cradle.
b. Disconnect any cables from the Ethernet connectors on the bottom of
the main control board in the control pod.
c. If used, disconnect the plug-in terminal block (TB1) on the bottom of
the main control board.
d. If an option module is installed, disconnect any I/O wiring terminal
blocks and remove the option module (not shown in image).
If a cable is not connected to the DPI port on the HIM cradle, be sure to leave the
protective cover installed.
=
Control Pod Shown Separated from the Drive for Clarity Only.
4b
4a
4c