Appendix F MicroLogix 1400 Distributed Network Protocol
DNP3 10K Event Logging
The number of events logged can be increased from 6013…10000 by utilizing
the memory space of Recipe and Data log. A status bit S:36/11 is used to
differentiate between the two DNP3 configurations on controller power up.
When the downloaded user program has S:36/11 bit set, on the next power
cycle, the 10000 event configuration is loaded. Similarly, if the downloaded
user program has S:36/11 bit reset to zero, on the next power cycle, the 6013
event logging configuration is loaded.
When the controller is configured for 10000 events logging, Recipe and/or
Data Logging operations are not allowed. If the user program has either of the
two configurations (DLG and/or RCP) when 10000 DNP3 event logging is