Calibrate the Analog
Voltage Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure and use this procedure.
.
1.
Double-click the icon to bring up the General parameter dialog.
You see the EDS Editor dialog ask you if you want to upload the
configuration from the device.
IMPORTANT
Apply power to the power supply and module for at least 10
minutes before calibrating the module. This allows internal
temperatures to stabilize, and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
4032
Power Supply Voltage
DeviceNet Input
250
Ω
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5
PDN OE2V
Voltage Meter