Publication 1734-UM001D-EN-P - April 2008
POINT I/O Module Data
99
Digital ac Input Modules
T
he 1734 digital ac input modules feature the following:
•
120 or 220V ac nominal are ac inputs
•
Input range of 65…132 for 120V ac inputs; 159…264 for 220V ac
inputs
•
Two sinking style inputs
•
Autobaud (will match baud of existing devices on the network)
•
Selectable input filter times (0…65 ms with 1 ms default)
•
Sequential auto addressing
Default Data Map for 1734-IB4D Module -
- Configuration Assembly Instance 103
Message Size: 18 Bytes
7
6
5
4
3
2
1
0
Consume 0
Input 0 Off to On Filter Byte 0
Consume 1
Input 0 Off to On Filter Byte 1
Consume 2
Input 0 On to Off Filter Byte 0
Consume 3
Input 0 On to Off Filter Byte 1
Consume 4
Input 1 Off to On Filter Byte 0
Consume 5
Input 1 Off to On Filter Byte 1
Consume 6
Input 1 On to Off Filter Byte 0
Consume 7
Input 1 On to Off Filter Byte 1
Consume 8
Input 2 Off to On Filter Byte 0
Consume 9
Input 2 Off to On Filter Byte 1
Consume 10
Input 2 On to Off Filter Byte 0
Consume 11
Input 2 On to Off Filter Byte 1
Consume 12
Input 3 Off to On Filter Byte 0
Consume 13
Input 3 Off to On Filter Byte 1
Consume 14
Input 3 On to Off Filter Byte 0
Consume 15
Input 3 On to Off Filter Byte 1
Consume 16
Autobaud Disable
Enable OW3
Enable OW2
Enable OW1
Enable OW0
Consume 17
Produced Assembly Instance
Produce (Tx)
No produced data
Where: OW = open wire.
Summary of Contents for 1734-IA2
Page 4: ...Publication 1734 UM001D EN P April 2008 4 Summary of Changes Notes ...
Page 12: ...Publication 1734 UM001D EN P April 2008 12 Table of Contents Notes ...
Page 77: ...Publication 1734 UM001D EN P April 2008 Install POINT I O Modules 77 ...
Page 78: ...Publication 1734 UM001D EN P April 2008 78 Install POINT I O Modules ...
Page 179: ...Publication 1734 UM001D EN P April 2008 Default Data Maps 177 Notes ...
Page 180: ...Publication 1734 UM001D EN P April 2008 178 Default Data Maps ...
Page 236: ...Publication 1734 UM001D EN P April 2008 234 Notes ...
Page 241: ......