Troubleshooting
•
Clear the Node Active check box in RSNetWorx for DeviceNet (if
using a DeviceNet scanner or DeviceNet adapter).
Module’s DeviceLogix program exits the Run mode unexpectedly
The module’s DeviceLogix program exits the Run mode unexpectedly. A
possible reason may be that the ADR feature of the scanner is turned on and
the ADR data of the module stored in the scanner is not consistent with what
is on the module. When the scanner establishes connection to the module, it
will verify the configuration in itself with what is in the module. Any mismatch
would result in the scanner downloading its saved ADR data to the module.
•
Check the ADR feature of the network scanner and verify if the
configuration stored in the scanner is the most recent and correct
version.