Protection Features
Safety Features
Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground. The
manufacturer conducts type and factory tests. Field tests can be conducted
with the appropriate test equipment, which applies the voltage with a slow
ramp (2 s up and 2 s down). Connect all input terminals together and connect
all output poles before conducting the test. When testing, set the cutoff
current settings to the values in the following table.
Figure 27 - Output Current Versus Ambient
Temperature
Figure 28 - Output Current Versus Altitude
Allowed Output Current at 48V
0
-25
0
20
40
70 °C
5
10
15
20
25
30 A
60
Ambient Temperature
A
B
A: 90…264V AC
B: 85…90V AC
short-term (4 s)
continuous
0
0
2000
4000
6000 m
5
10
15
20
25
30 A
continuous
Altitude
A: Tamb <60 °C
B: Tamb <50 °C
C: Tamb <40 °C
A
B
C
short-term (4 s)
Allowed Output Current at 48V
Attributes
Values
Notes
Output protection
Electronically protected against overload, no-load, and short-circuits
(1)
(1) An audible noise occurs if there is a protection event.
Output overvoltage protection
58.8V DC typ
If there is an internal power supply anomaly, a redundant circuit limits
the maximum output voltage. The output shuts down and automatically
attempts to restart.
60V DC max
Degree of protection
IP 20
EN/IEC 60529
(2)
(2) For use in a controlled environment according to CSA 22.2 No 107.1-01.
Penetration protection
>5 mm (0.2 in.)
For example, screws and small parts
Over-temperature protection
Yes
Output shutdown with automatic restart
Input transient protection
MOV
Metal Oxide Varistor
Internal input fuse
Included
Not user-replaceable
Attributes
Values
Notes
Input/output separation
(1)
(1) Double or reinforced insulation.
SELV
IEC/EN 60950-1
PELV
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
Class of protection
I
PE connection not required.
Isolation resistance
>100 M
Ω
Input to output, 500V DC
PE resistance
<0.1
Ω
—
Touch current
(leakage current)
Typ
0.39 mA/1.0 mA
100V AC, 50 Hz, TN-, TT-mains/IT-mains
Typ
0.56 mA/1.43 mA 120V AC, 60 Hz, TN-, TT-mains/IT-mains
Typ
0.90 mA/2.25 mA 230V AC, 50 Hz, TN-, TT-mains/IT-mains
Max
0.50 mA/1.21 mA 110V AC, 50 Hz, TN-, TT-mains/IT-mains
Max
0.71 mA/1.73 mA 132V AC, 60 Hz, TN-, TT-mains/IT-mains
Max
1.18 mA/2.28 mA 264V AC, 50 Hz, TN-, TT-mains/IT-mains