R8MUSTLED-01
INSTRUCTION MANUAL
The emergency lighting must be inspected and tested
regularly in accordance with local codes of practice:
note: for safety reasons tests should be carried out
during daylight hours.
The minimum recommended test schedule is as follows:
After installation, allow 24 hours to ensure full battery
charge and then interrupt the supply; the maximum
duration time is 3 hours check that LEDs are still
lighting.
1. Daily check that charge indicator LED is working
2. Monthly, interrupt mains for a short period and
check LED lights
3. Annual 12 month check, full duration test.
Interrupt mains supply, LEDs will light and
should last for a minimum 3 hours operation:
batteries must be replaced when they can no
longer support 3 hour operation.
4. Complete record sheet on installation and retain in
maintenance file.
5. Update file with ongoing test records for inspection
by fire officer or other duly authorised person
Testing
De noodverlichting moet regelmatig worden gecontroleerd en
getest in overeenstemming met de plaatselijke praktijkrichtlijnen.
Opmerking: om veiligheidsredenen moeten testen tijdens
daglichturen worden uitgevoerd. Het minimum aanbevolen
testschema ziet er als volgt uit:
Na installatie 24 uur wachten om ervoor te zorgen dat de batterij
volledig is opgeladen en daarna de stroomvoorziening
onderbreken; de maximum duur is 3 uur. Controleer of de leds
nog licht geven.
1. Controleer dagelijks of de ladingindicator van de led werkt.
2. Schakel maandelijks de stroomvoorziening even uit en
controleer de ledlampen.
3. Verricht jaarlijks een complete inspectie, een test van volledige
duur. Schakel de stroomvoorziening uit. De leds zullen oplichten
en dienen ten minste 3 uur mee te gaan. De batterijen moeten
worden vervangen als ze geen 3 uur meer werken.
4. Vul het registratieblad van de installatie in en bewaar in het
onderhoudsbestand.
5. Werk het bestand bij met de verschillende testresultaten ter
inspectie van de brandweer of een andere naar behoren
bevoegde persoon.
Testen
UNIVERSAL EMERGENCY LED
FITTING SELF TEST, WHITE
R8MUSTLED-01
ZELFTEST VAN UNIVERSELE
NOODVERLICHTING, WIT
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product,
consult a competent electrician
Note:
Product technical information and specification may change over time without prior notification. For the latest technical
information please visit our web site www.ledgrouprobus.com or robusdirect.com
Issue 2 080914
Page 1
Information for the Product user:
Installation
1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste
(WEEE marked with crossed out wheelie bin symbol).
2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre
for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.
3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly. It is
important that it is separated from normal household waste and recycled in the WEEE chain
4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household
waste, but should be disposed of according to local WEEE regulations
The Installation must be carried out by a qualified electrician
1. Ensure mains supply is switched off before commencing work.
2. Safety note! The power supply cord must not be exposed to
mechanical damage.
3. presse the latch on the two sides of unit, and then slide the
diffuser off
4. Disassemble the fitting base from the fitting by removing two
screws.
5. Mark appropriate fixing position on the ceiling or wall, Before
drilling establish the
direction of buried cables and other building services.
a) Surface Mounting: please note that the fixing centres
distance are 152mm. Drill holes in the ceilling.
b) Recessed Mounting: Cut out the hole (size is 290x140mm),
Remove the recess covers from two sides of the fitting
base. and loosen the two screws so that get out the handles.
6. Fix fitting base to the ceiling,ensure it is secure.
7. Introduce supply cables into the base.
8. Connect wires from un-switched supply to terminals: Brown
/Live to PL, Blue/ Neutral to N and Green/ Yellow to earth. For
fitting always on , link terminal “SL” to terminal “PL”. When
controlled by switch connect switched live wire to terminal SL
and permanent live to PL.
Note: if “SL” terminal not connected, fitting works as
non-maintained
9. Refit LED plate to base and ensure that it fits securely.
10. Attach diffuser to base through the latch
Switch on supply:
The green led should come on indicating correct battery charge
status, all LEDs will come on. When supply to the switched live
PL is lost, battery will operate fitting in emergency mode.
1. Zorg dat het lichtnet is uitgeschakeld voordat u begint.
2. Veiligheidsopmerking! Het stroomsnoer mag niet worden blootgesteld aan
mechanische beschadiging.
3. Druk op de vergrendeling aan beide zijden van de eenheid en schuif dan de
lichtverspreider eraf
4. Demonteer de basis van het armatuur door twee schroeven te verwijderen.
5. Markeer de gepaste bevestigingspositie op het plafond of de muur,
controleer vóór het boren op verborgen kabels en andere voorzieningen
van het gebouw.
a) Oppervlaktemontage: gelieve er rekening mee te houden dat de afstand
tussen de bevestigingspunten 152 mm bedraagt. Boor gaten in het
plafond.
b) Verzonken montage: Breng de uitsparing aan (afmetingen 290x140mm),
Verwijder de verzinkingsplaten van beide zijden van de basis van het
armatuur en draai de twee schroeven los om de handgrepen vrij te geven.
6. Bevestig de basis van het armatuur tegen het plafond, zorg dat deze goed
vast zit.
7. Steek de stroomkabels in de basis.
8. Sluit de draden van de uitgeschakelde stroomvoorziening aan op de
aansluitklemmen: Bruin/Stroom op PL, Blauw/Neutraal op N en Groen/Geel
op aarding. Verbind om de verlichting permanent aan te hebben de
aansluitklem "SL" met de aansluitklem "PL". Wanneer de lamp wordt
bediend met een schakelaar, verbind dan de geschakelde stroomdraad met
aansluitklem SL en de permanente stroomdraad op PL. Opmerking: als
geen aansluiting wordt gemaakt op de aansluitklem “SL”, werkt de
verlichtingsarmatuur als niet-zelfstandig
9. Plaats de LED-plaat terug op de basis en zorg dat deze goed vast zit.
10. Bevestig de lichtverspreider aan de basis aan de hand van de
vergrendeling.
Schakel de stroom in: De groene led moet gaan branden om de juiste
laadstatus van de batterij aan te geven, alle LED's gaan branden. Wanneer de
voeding van de geschakelde stroomdraad PL wordt onderbroken, wordt de
verlichtingsarmatuur in noodbedrijf gevoed door de batterij
5°C < Ta < +40°C, 220V – 240V ~ 50/60Hz, Class I, IP20
Suitable for mounting on a normally flammable surface
5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz, Class I, IP20
Geschikt voor montage op normaal ontvlambaar oppervlakte
Installatie
LEES DE INSTRUCTIES VOORDAT U BEGINT MET DE INSTALLATIE EN HOU DIT BIJDEHAND VOOR LATER.
! Elektrische producten kunnen de dood of letsel veroorzaken of eigendommen beschadigen. Als u twijfelt over de installatie of
het gebruik van dit product, raadpleeg dan een erkende elektricien
Opmerkingen:
Technische gegevens en specificaties van dit product kunnen zonder voorafgaande kennisgeving wijzigen. Ga voor de meest
recente technische gegevens naar onze website www.ledgrouprobus.com of robusdirect.com
Informatie voor de gebruiker van het product:
1. Hou bij het verwijderen van afval rekening met de regeling voor afgedankte elektrische en elektronische apparatuur, gescheiden van
gewoon huishoudelijk afval (AEEA, pictogram van een kliko met een kruis erdoorheen).
2. Neem uw verantwoordelijkheid op het vlak van hergebruik en recycling door dit product aan het einde van zijn levenscyclus in te
leveren bij een inleverpunt voor elektronisch afval, een milieupark of een winkel waar u een nieuw product koopt.
3. Deze apparatuur kan stoffen bevatten die gevaarlijk zijn voor de gezondheid en het milieu indien ze onachtzaam wordt weggegooid.
Het is belangrijk dat ze gescheiden gehouden wordt van het normaal huishoudelijk afval en gerecycled wordt in het netwerk voor
AEEA.
4. Het pictogram van een kliko met een kruis erdoorheen op een product betekent dat dit apparaat niet samen met het gewone
huishoudelijk afval mag worden weggegooid, maar dat het dient te worden verwijderd in overeenstemming met de lokale regelgeving
voor AEEA (afgedankte elektrische en elektronische apparatuur).
De installatie dient te worden uitgevoerd door een elektricien
EN
NL
LED FUNCTIONS GUIDE
Green
Yellow
*Fast flash
*Slow flash
●
●
Red
Status
Normally charging mode
Battery insufficient capacity
Lamp replacement required or
lamp not inserted incorrectly
Self-test or manual test
Normally emergency
discharging
●
BESCHRIJVING LEDFUNCTIES
Groen
Geel
* Snel knipperen
* Langzaam knipperen
●
●
Rood
Status
Normaal laden
Batterij bijna leeg
Lamp moet worden vervangen of lamp
niet correct geplaatst
Zelftest of handmatige test
Normale noodontlading
●