Robus R8MUSTLED-01 Instruction Manual Download Page 1

R8MUSTLED-01

INSTRUCTION MANUAL

The emergency lighting must be inspected and tested 

regularly in accordance with local codes of practice: 

note: for safety reasons tests should be carried out 

during daylight hours.

The minimum recommended test schedule is as follows:

After installation, allow 24 hours to ensure full battery 

charge and then interrupt the supply; the maximum 

duration time is 3 hours check that LEDs are still 

lighting. 

1. Daily check that charge indicator LED is working

2. Monthly, interrupt mains for a short period and   

    check LED lights

3. Annual 12 month check, full duration test. 

    Interrupt mains supply, LEDs will light and 

    should last for a minimum 3 hours operation: 

    batteries must be replaced when they can no 

    longer support 3 hour operation.

4. Complete record sheet on installation and retain in 

    maintenance file.

5. Update file with ongoing test records for inspection 

    by fire officer or other duly authorised person

Testing

De noodverlichting moet regelmatig worden gecontroleerd en 
getest in overeenstemming met de plaatselijke praktijkrichtlijnen. 
Opmerking: om veiligheidsredenen moeten testen tijdens 
daglichturen worden uitgevoerd. Het minimum aanbevolen 
testschema ziet er als volgt uit:
Na installatie 24 uur wachten om ervoor te zorgen dat de batterij 
volledig is opgeladen en daarna de stroomvoorziening 
onderbreken; de maximum duur is 3 uur. Controleer of de leds 
nog licht geven. 

1. Controleer dagelijks of de ladingindicator van de led werkt.
2. Schakel maandelijks de stroomvoorziening even uit en 
controleer de ledlampen.
3. Verricht jaarlijks een complete inspectie, een test van volledige 
duur. Schakel de stroomvoorziening uit. De leds zullen oplichten 
en dienen ten minste 3 uur mee te gaan. De batterijen moeten 
worden vervangen als ze geen 3 uur meer werken.
4. Vul het registratieblad van de installatie in en bewaar in het 
onderhoudsbestand.
5. Werk het bestand bij met de verschillende testresultaten ter 
inspectie van de brandweer of een andere naar behoren 
bevoegde persoon.

Testen

UNIVERSAL EMERGENCY LED 

FITTING SELF TEST, WHITE

R8MUSTLED-01

ZELFTEST VAN UNIVERSELE

NOODVERLICHTING, WIT

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.

! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or use of this product, 

consult a competent electrician

                                                                                                           Note:

Product technical information and specification may change over time without prior notification. For the latest technical 

information please visit our web site www.ledgrouprobus.com or robusdirect.com

Issue 2 080914

Page 1

Information for the Product user:

Installation

1. Please note the requirement to dispose of Waste Electrical & Electronic Equipment separately from household waste 

    (WEEE marked with crossed out wheelie bin symbol). 

2. Please consider your role in contributing to re-use and recycling by returning this product at end of life to a collection centre 

    for waste electrical equipment or a Civic Amenity site, or to a retail outlet from which you are purchasing a replacement.

3. This equipment may contain substances that are hazardous to health and the environment if disposed of carelessly.  It is 

    important that it is separated from normal household waste and recycled in the WEEE chain

4. The “crossed out wheelie bin symbol” on a product indicates this equipment must not be disposed of in normal household 

    waste, but should be disposed of according to local WEEE regulations

The Installation must be carried out by a qualified electrician

1. Ensure mains supply is switched off before commencing work.  

2. Safety note! The power supply cord must not be exposed to 

    mechanical damage.

3. presse the latch on the two sides of unit, and then slide the 

    diffuser off 

4. Disassemble the fitting base from the fitting by removing two 

    screws.

5. Mark appropriate fixing position on the ceiling or wall, Before 

    drilling establish the 

    direction of buried cables and other building services. 

    a) Surface Mounting: please note that the fixing centres 

        distance are 152mm. Drill holes in the ceilling.

    b) Recessed Mounting: Cut out the hole (size is 290x140mm), 

       Remove the recess covers from two sides of the fitting 

       base. and loosen the two screws so that get out the handles. 

6. Fix fitting base to the ceiling,ensure it is secure.

7. Introduce supply cables into the base.

8. Connect wires from un-switched supply to terminals: Brown 

     /Live to PL, Blue/ Neutral to N and Green/ Yellow to earth. For 

    fitting always on , link terminal “SL” to terminal “PL”. When 

    controlled by switch connect switched live wire to terminal SL 

    and permanent live to PL.

    Note: if “SL” terminal not connected, fitting works as 

    non-maintained

9. Refit LED plate to base and ensure that it fits securely.

10. Attach diffuser to base through the latch 

Switch on supply:

The green led should come on indicating correct battery charge 

status, all LEDs will come on. When supply to the switched live 

PL is lost, battery will operate fitting in emergency mode.

1. Zorg dat het lichtnet is uitgeschakeld voordat u begint.
2. Veiligheidsopmerking! Het stroomsnoer mag niet worden blootgesteld aan 
    mechanische beschadiging.
3. Druk op de vergrendeling aan beide zijden van de eenheid en schuif dan de 
    lichtverspreider eraf
4. Demonteer de basis van het armatuur door twee schroeven te verwijderen.
5. Markeer de gepaste bevestigingspositie op het plafond of de muur, 
    controleer vóór het boren op verborgen kabels en andere voorzieningen 
    van het gebouw.
    a) Oppervlaktemontage: gelieve er rekening mee te houden dat de afstand 
        tussen de bevestigingspunten 152 mm bedraagt. Boor gaten in het 
       plafond.
    b) Verzonken montage: Breng de uitsparing aan (afmetingen 290x140mm), 
       Verwijder de verzinkingsplaten van beide zijden van de basis van het
       armatuur en draai de twee schroeven los om de handgrepen vrij te geven.
6. Bevestig de basis van het armatuur tegen het plafond, zorg dat deze goed 
    vast zit.
7. Steek de stroomkabels in de basis.
8. Sluit de draden van de uitgeschakelde stroomvoorziening aan op de 
    aansluitklemmen: Bruin/Stroom op PL, Blauw/Neutraal op N en Groen/Geel 
    op aarding. Verbind om de verlichting permanent aan te hebben de 
    aansluitklem "SL" met de aansluitklem "PL". Wanneer de lamp wordt 
    bediend met een schakelaar, verbind dan de geschakelde stroomdraad met 
    aansluitklem SL en de permanente stroomdraad op PL. Opmerking: als 
    geen aansluiting wordt gemaakt op de aansluitklem “SL”, werkt de 
    verlichtingsarmatuur als niet-zelfstandig
9. Plaats de LED-plaat terug op de basis en zorg dat deze goed vast zit.
10. Bevestig de lichtverspreider aan de basis aan de hand van de 
      vergrendeling. 

Schakel de stroom in: De groene led moet gaan branden om de juiste
laadstatus van de batterij aan te geven, alle LED's gaan branden. Wanneer de 
voeding van de geschakelde stroomdraad PL wordt onderbroken, wordt de 
verlichtingsarmatuur in noodbedrijf gevoed door de batterij

  

5°C < Ta < +40°C, 220V – 240V ~ 50/60Hz, Class I, IP20

Suitable for mounting on a normally flammable surface

5°C < Ta < +25°C, 220V – 240V ~ 50/60Hz, Class I, IP20

Geschikt voor montage op normaal ontvlambaar oppervlakte

Installatie

LEES DE INSTRUCTIES VOORDAT U BEGINT MET DE INSTALLATIE EN HOU DIT BIJDEHAND VOOR LATER.

! Elektrische producten kunnen de dood of letsel veroorzaken of eigendommen beschadigen. Als u twijfelt over de installatie of 

het gebruik van dit product, raadpleeg dan een erkende elektricien

                                                                                                    Opmerkingen: 

Technische gegevens en specificaties van dit product kunnen zonder voorafgaande kennisgeving wijzigen. Ga voor de meest 

recente technische gegevens naar onze website www.ledgrouprobus.com of robusdirect.com

Informatie voor de gebruiker van het product:

1. Hou bij het verwijderen van afval rekening met de regeling voor afgedankte elektrische en elektronische apparatuur, gescheiden van 

    gewoon huishoudelijk afval (AEEA, pictogram van een kliko met een kruis erdoorheen).

2. Neem uw verantwoordelijkheid op het vlak van hergebruik en recycling door dit product aan het einde van zijn levenscyclus in te 

    leveren bij een inleverpunt voor elektronisch afval, een milieupark of een winkel waar u een nieuw product koopt.

3. Deze apparatuur kan stoffen bevatten die gevaarlijk zijn voor de gezondheid en het milieu indien ze onachtzaam wordt weggegooid. 

    Het is belangrijk dat ze gescheiden gehouden wordt van het normaal huishoudelijk afval en gerecycled wordt in het netwerk voor 

    AEEA.

4. Het pictogram van een kliko met een kruis erdoorheen op een product betekent dat dit apparaat niet samen met het gewone 

    huishoudelijk afval mag worden weggegooid, maar dat het dient te worden verwijderd in overeenstemming met de lokale regelgeving 

    voor AEEA (afgedankte elektrische en elektronische apparatuur).

De installatie dient te worden uitgevoerd door een elektricien

EN

NL

LED FUNCTIONS GUIDE

Green

Yellow

*Fast flash

*Slow flash

Red

Status

Normally charging mode

Battery insufficient capacity

Lamp replacement required or 
lamp not inserted incorrectly

Self-test or manual test

Normally emergency 
     discharging

BESCHRIJVING LEDFUNCTIES

Groen

Geel

* Snel knipperen

* Langzaam knipperen

Rood

Status

Normaal laden

Batterij bijna leeg

Lamp moet worden vervangen of lamp 
niet correct geplaatst

Zelftest of handmatige test

Normale noodontlading

Reviews: