background image

Issue 2 080715

30W LED PANEL LIGHT,

300X1200MM, WHITE TRIM

R1230LEDCW-01

R1230LEDDW-01

1. Ensure mains supply is switched off before commencing 
    work.
2. Remove 300 x 1200mm tile from ceiling.
3. Ensure the area above the fitting is free from obstacle 
    pipes cable tray etc.
4. Connect plug to AC supply
5. Ensure the connections going to and from the driver 
    are secure.
6. Place connector, drivers and cable into the ceiling void.
7. Offer luminaire up to the ceiling void and manoeuvre into 
    final position similar to standard ceiling tile. 
8.This product has no user serviceable parts. If any part is 
   damaged, disconnect from mains and discontinue use.

Page 1

The Installation must be carried out by an electrician

INSTRUCTION MANUAL

PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
! Electrical products can cause death or injury, or damage to property. If in any doubt about the installation or
use of this product, consult a competent electrician
                                                                                                          Note:
Product technical information and specification may change over time without prior notification. For the latest 
technical information please visit our web site www.ledgrouprobus.com.au 

LED Group ROBUS Australia 

9/210 Queensport Road North     Tel: +61 73893 1488

Murarrie                                        Fax: +61 73112 1927

QLD 4172                                     Email: [email protected]

Australia                                       Website: www.ledgrouprobus.com.au 

Model No.
Voltage:                
Power:                                                         
Lumen:                                  
CCT:                                      
CRI:                                                                 
Beam Angle:
PF:        

                                                       

                                                

Ta Range:                               
IP Rating:
IK Rating:                                      
Safety Class:                                                           
Dimensions:                             
Depth:                                                           
Weight:                                                                           
Warranty:                                               
Installation:                             
                                                

Complete with flex and AU plug
Suitable for mounting on normally flammable surface
Minimum distance from illuminated object is 0.5 metre
Driver must never be “hot-plugged” or connected to the
fitting when live.
Doing this may damage the fitting and will void the warranty.
Complies with EN 60598-1, EN 60598-2-2, IEC 62471-2, IEC 
62778, IEC 62493, IEC 61347-1, 61347-2-13

R1230LEDCW-01 
220-240V~50/60Hz               
30W                                           
2800lm                        
4000K                            
80                                                      
110

o                                                                     

                                                

0.9
-20°C < ta < +45°C        
20
06                                  
Class II for the driver                                                      
295mm X 1195mm                      
9mm                             
3.8Kg                                              
5 year                           
Recessed mounted, 
Box mounted,  
Suspended

 

R1230LEDDW-01 
220-240V~50/60Hz               
30W                                           
3150lm                        
5000K                            
80                                                      
110

o                                                                     

                                                

0.9
-20°C < ta < +45°C        
20
06                                  
Class II for the driver                                                      
295mm X 1195mm                      
9mm                             
3.8Kg                                              
5 year                           
Recessed mounted, 
Box mounted,  
Suspended

 

Specifications

Installation  

ISO 9001:2008

Q UAL IT Y ASSU RED CO MPANY

Warning:

Luminaire marked as NON-IC according to ASNZS60598-2.2. 

Not suitable for use on residential properties. 

DO NOT COVER OR ABUT. Any insulation material must be 

positioned at a minimum distance of 100 mm from the fitting.

Caution:

Recessed Luminaires may pose an increased risk of fire

or property damage if not installed according to the

instructions provided.

  

Safety Instructions  

Luminaires not suitable for 
covering with thermally
insulating material.

Joist 

Driver 

SCB

HCB

MIC

SCI

DANGER - RISK OF FIRE

- Shall not be installed in residential premises 

SCI = 100mm  MIC = 100mm 

SCB = 50mm  HCB = 25mm