Features and technical data
20
1
Figure 1.17
AY10+S70 electronic boards
TL
Limit thermostat connector
ENC
Knob
EV
Gas solenoid valve connector
LS
Gas valve ON signal lamp connector
P1
6 pole flame controller connector
TF
Exhausted gas thermostat connector
PD
System water differential pressure switch
A1, A2 Auxiliary inputs
J2
System water circulator jumper
N.O. CONTACT
System water circulating pump control terminals (max 700 W)
V3V (1-2-N)
Appliance circulation pump connecting terminals
MAIN
230V (L, N) Board power supply 230 Vac
IGN.BOX (L, N)
Flame controller power supply 230 Vac
P1
Connector for blower drive
THRC
Return hot water temperature connector
THMC Delivery hot water temperature connector
TA2-TA1 Auxiliary temperature probes connector
J1
CAN bus Jumper
P8
(GND, L, H) CAN bus connector
P7
(R, W, 0) Enable input
FS5
Board supply connector
F1-F2
Fuses
1.6
CONTROLS
Control device
The appliance may only work if it is connected to a control de-
vice, selected from:
▶
(1) pre-configured DDC control
▶
(2) external enables
1.6.1
Adjustment system (1) with pre-configured
DDC control
The main functions are:
▶
Adjustment and control of the GAHP/GA unit and AY00-120
unit in cascade (ON/OFF mode).
▶
Data display and parameters setting.
▶
Hourly programming.
▶
Climatic curve control.
▶
Diagnostics.
▶
Errors reset.
▶
Possibility to interface with a BMS.
DDC functionality may be extended with auxiliary Robur devices
RB100 and RB200 (e.g. service requests, DHW production, Third
Party generator control, probe control, system valves or circulat-
ing pumps, ...).
1.6.2
Adjustment system (2) with external enables
The appliance may also be controlled via generic enable devic-
es (e.g. thermostats, timers, buttons, contactors...) fitted with
voltage-free NO contacts. This system only provides elementary
control (on/off, with fixed setpoint temperature), without the
important functions of system (1). Control of the cascade be-
tween GAHP/GA and AY00-120 is left to the user.
For connection of the selected device to the appliance's
electronic board please refer to Paragraph 4.4