Features and technical data
Installation, use and maintenance manual – GAHP A
7
1
1
FEATURES AND TECHNICAL DATA
1.1
FEATURES
Operation
Based on the thermodynamic water-ammonia absorption cycle
(H
2
0–NH
3
), the appliance produces hot water using outdoor air
as a renewable energy source (cold source) and natural gas (or
LPG) as primary energy.
The thermodynamic cycle takes place within a hermetically
sealed circuit, in welded construction, perfectly tight, facto-
ry-tested, which does not require any maintenance or coolant
top-ups.
Mechanical and thermo-hydraulic components
▶
steel sealed circuit, externally treated with epoxy paint;
▶
sealed combustion chamber (type C) suitable for outdoor
installations;
▶
metal mesh radiant burner equipped with ignition and flame
detection device, controlled by an electronic control unit;
▶
titanium stainless steel shell-and-tube water heat exchang-
er, externally insulated;
▶
stainless steel, flue gas latent heat recovery exchanger;
▶
air exchanger with finned coil, with steel pipe and alumini-
um fins;
▶
automatic microprocessor-controlled finned coil automatic
defrosting valve;
▶
standard or S1 silenced fan (reduction of electrical consump-
tion and reduction of sound emission).
Control and safety devices
▶
S61 electronic board with microprocessor, LCD display and
knob;
▶
Mod10 additional electronic board (integrated in S61);
▶
auxiliary W10 electronic board
▶
installation water flowmeter;
▶
generator limit thermostat, with manual reset;
▶
flue gas temperature thermostat, with manual reset;
▶
generator fin temperature sensor;
▶
sealed circuit safety relief valve;
▶
by-pass valve, between high and low pressure circuits;
▶
ionisation flame controller;
▶
gas solenoid valve with double shutter;
▶
antifreeze function for water circuit;
▶
condensate discharge obstruction sensor.
Standard or silenced fan
According to the type of fan the GAHP A unit is available in two
versions:
▶
standard fan, for applications that do not require a special
degree of noiselessness;
▶
silenced fan, for applications that require a high degree of
noiselessness;
1.2
DIMENSIONS
Figure 1�1
Service plate - Hydraulic/gas unions detail
G
Gas fitting Ø ¾” F
B
Inlet water fitting Ø 1¼” F
A
Outlet water fitting Ø 1¼” F