Memory Mapping
6-34
Robostar Co., Ltd
6.3.17
Write GLOBAL Integer
PLC(PC)
-> N1 Series
N1 Series
-> PLC(PC)
GINT Index 입력
H
L
H
L
H
L
GINT Value 입력
Write Enable Flag
Write Complete Flag
H
L
Integer Index
Integer Index
Integer Value
Integer Value
T1
T3
T2
Description :
Set the values of Global Integer Index and Global Integer to write.
Set Write Enable Flag to High.
When the saving process is completed in N1 Series, Write complete Flag changes from Low
to High.
When setting Write Enable Flag to Low, Write Complete Flag Bit is changed to Low.
In case of saving Global Integer values continually, a delay time of T2(30ms) is required.
GLOBAL Integer, GLOBAL Float, GLOBAL Point commonly use Read Enable Flag so
caution should be taken in setting the Index value of an unused variable at a time
when no change is desired.