background image

TROUBLESHOOTING GUIDE

780-704/780-705

MODERNIZATION KITS

SEQUENCE OF OPERATION AND SYSTEM CHECKOUT 
PROCEDURES

The initial installation portion is now complete and ready for final 

 

system checkout. The checkout procedures listed below must be 

 

followed. While there are redundant safety features built into the 

 

system, it is imperative that you follow the steps outlined below to 

 

ensure proper and safe operation. If you encounter any irregularities, 
refer to the 

TROUBLESHOOTING GUIDE

1. 

 Check all wiring connections.

2. 

 Turn on main gas supply and manual valve on the gas valve.

3. 

❏ 

Turn on electrical power.

4. 

 Thermostat set high.

5. 

 Sparking begins, pilot gas ignites.

6. 

 Pilot flame on sensor, main burner on.

7. 

 With main burner on, cycle thermostat 

off

 then 

on

.

A. Nonlockout system will turn off and immediately on again.
B. Lockout system will turn off. Sparking will not begin for 5 

 

seconds.

8. 

 With the main burner on, turn the manual gas valve to 

off  

 

  position. Wait until all flame is out. Turn manual gas valve 

 

 

  on again.

A. Sparking will begin as soon as the pilot flame is out.
B. Pilot ignition takes place when gas flow is restored.

9. 

 If this is a lockout system, with main burner on, turn manual gas 

 

 

  valve off. Sparking will begin when the pilot flame goes out. After 

 

 

  60 seconds the system will lockout and sparking will cease.

10. 

 To restart the system turn thermostat low for 5 seconds. Then set 

 

 

  high again. Sparking will begin in 5 seconds.

11. 

 It is absolutely necessary that the system be cycled normally 

 

 

  (thermostatically controlled) through at least three complete 

 

 

  heating cycles. Set thermostat to a temperature slightly higher 

 

 

  than the existing ambient. Allow appliance to cycle ON and run 

 

 

  through a normal cycle. Do not manually shorten the cycle.

12. 

 The initial checkout procedures have been completed. If the 

 

 

  system has functioned normally, return thermostat setting to its 

 

 

  normal setting. The qualified installing agency must completely fill 

 

 

  out and apply the yellow appliance conversion sticker to the front 

 

 

  of the appliance. Leave these and all other instructions with 

 

 

  the homeowner.

TROUBLESHOOTING GUIDE
FLAME RECTIFICATION IGNITION CONTROL UNITS 
SP715/SP735

THERE ARE FIVE POTENTIAL PROBLEM CONDITIONS WITH THE 
THERMOSTAT SET HIGH:

1.  Thermostat on, no spark, no pilot gas.
2.  Have spark, no pilot gas flow.
3.  Have pilot gas, no spark.
4.  Have pilot flame, main burner does not turn on.
5.  Short-cycling of main burner. Main burner turns off before the 

 

  thermostat is satisfied.

TO PERFORM THE FOLLOWING TEST YOU WILL NEED 
A VOLT OHM METER.

PROBLEM #1: Thermostat on, no spark, no pilot gas.
Possible Causes

A  No main power
B.  Faulty transformer
C.  Faulty thermostat
D.  Faulty limit
E.  Faulty ignition control unit

SOLUTION:

1.  With power on and thermostat set high, set your test meter to the 

 

  24 volt scale. Probe terminals TH and TR. If you do not read 24 volts, 

 

  the problem is not in the ignition system. Perform normal system 

 

  checks of main power, transformer, thermostat and the limit control. 

 

  If you do read 24 volts at TH and TR the problem is in the ignition 

 

  system. Check for loose or defective wiring. If wiring is good replace 

 

  the ignition control unit. See your Uni-Line wholesaler for order 

 

  numbers.

PROBLEM #2: Have spark, no pilot gas flow.

Possible Causes

A.  Main gas supply turned off
B.  Manual valve on gas valve turned off
C.  Faulty primary valve in the gas valve
D.  Faulty wire connection
E.  Faulty ignition unit

SOLUTION: Set test meter to 24 volt scale.

1.  Be sure main gas valve and manual valve are turned on.
2.  With gas on and the system sparking probe terminal TR and the blue 

 

  wire terminal on the solenoid on the 7000 gas valve. With 24 volts at 

 

  these terminals and pilot gas does not flow, replace the solenoid in 

 

  the 7000 gas valve.
3.  If you do not read 24 volts at the solenoid valve terminals, probe 

 

  terminals PV and MV/PV on the ignition control unit. If you read 24 

 

  volts here but not at the gas valve, there is a loose wire connection 

 

  in the blue or white wire. Repair the wire connection.
4.  If you do not read 24 volts at terminals PV and MV/PV replace the 

 

  ignition control unit. 

Reviews: