![Roberts Gorden NDUSTRIA NHE Series Installation, Operation & Service Manual Download Page 18](http://html.mh-extra.com/html/roberts-gorden/ndustria-nhe-series/ndustria-nhe-series_installation-operation-and-service-manual_1469688018.webp)
NHE-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
14
FIGURE 13: Critical Hanger Placement
Description
Part Number
S-Hook
91907302
Tube/Reflector Hanger
030901XX
Run Length
Typical Expansion
Minimum “X” Length
10' (3 m) - 50' (15 m)
±1" (3 cm)
12" (305 mm)
51' (15 m) - 60' (18 m)
±2" (5 cm)
18" (457 mm)
61' (18 m) - 70' (24 m)
±3" (8 cm)
24" (609 mm)