![Roberts Gorden NDUSTRIA NHE Series Installation, Operation & Service Manual Download Page 13](http://html.mh-extra.com/html/roberts-gorden/ndustria-nhe-series/ndustria-nhe-series_installation-operation-and-service-manual_1469688013.webp)
SECTION 5: M
AJOR
C
OMPONENTS
9
SECTION 5: MAJOR COMPONENTS
FIGURE 12: Major Component Descriptions
Burner with Tube
Gasket
Must be installed
with the flame
observation window
facing down.
Standard
Reflector
(Aluminum or
Stainless
Steel)
Alternate overlap as
shown on overview and
. Minimum
overlap is 6" (16 cm).
Tube and Reflector Hanger
with Clamp Package
Position this hanger no more
than 4" (10 cm) away from the
burner.
Coupling Assembly
with Lock
Reflector End Cap
Punch out center
section to
accommodate tube.
Tube and Reflector Hanger
Suspend system from these
hangers.
Flex Gas Line with
Shut Off Cock
Tube
Hot rolled or heat
treated aluminized tube
supplied in 10' (3 m) lengths.
Reflector Support Strap &
Wire Form
Vent Adapter
Burner Tube
Supplied in 10' (3 m) lengths.
Burner tube is always the first
tube after the burner.
Combustion Air
Weather Vent
Attach at flue end
and air inlet
where required.
Turbulator/Swirler
Install turbulator/Swirler as
specified in the "Turbulator/
Swirler Installation" chart.
See
and Page 22
.
Summary of Contents for NDUSTRIA NHE Series
Page 2: ......
Page 4: ......
Page 21: ...SECTION 6 HEATER INSTALLATION 17 FIGURE 16 Linear Heater Layout Overview ...
Page 37: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 33 FIGURE 26 U Tube Heater Layout Overview ...
Page 69: ...SECTION12 TROUBLESHOOTING 65 ...
Page 74: ...NHE SERIES INSTALLATION OPERATION AND SERVICE MANUAL 70 ...