SECTION 3: I
NSTALLATION
15
3.2 Positioning CORAYVAC
®
Modulating Heating
Control
3.2.1
For serviceability, it is convenient to mount the
controller at occupant level in the vicinity of the
pump. For proper frequency between the VFD and
pump, the wire length between controller and vac-
uum pump should not be more than 100' (30 m). A
Load Reactor (P/N 100610XX) will be required for
distances greater than 100' (30 m). Maximum dis-
tance with Load Reactor is 400' (120 m). Load reac-
tor should be mounted as close to VFD as possible.
Consult factory if distance required is greater.
Do not mount controller outdoors.
Controller must
not be installed where subjected to adverse condi-
tions such as: combustible, oily, or hazardous vapors
or dust; excessive moisture or dirt; vibration. To avoid
damage from possible condensation leaks, do not
mount controller directly beneath pump. Avoid install-
ing the controller in mezzanines, direct sunlight, or
near external heat sources because these locations
usually have unpredictable temperature rises.
FIGURE 7: Controller Mounting - CORAYVAC
®
Modulating Heating Control
(Dimensions shown in inches)
FIGURE 8: Controller Mounting - COMPLETE™
Modulating Heating Control
(Dimensions shown in inches)
Note:
A paper mounting template is included with the
CORAYVAC
®
Modulating Heating Control and the
COMPLETE™ Modulating Heating Control panels.
Appropriately position the template on the mounting
surface, ensuring the template is level prior to mark-
ing each mounting hole shown on template. Pre-drill
mounting holes using a 9/32" drill bit. Position control
0.33
R0.16
R0.16
19.00
1.5 TYP.
1.5 TYP
1.5 TYP.
19.00
0.51
R0.27
R0.16
21.36
0.51
1.50
0.33
R0.16
R0.16
1.5 TYP
1.5 TYP.
0.51
R0.27
R0.16
0.51
1.50
17.88
11.00
11.00
17.88
R0.16
R0.27
Summary of Contents for CORAYVAC
Page 2: ......
Page 4: ......
Page 69: ...SECTION 8 PROGRAMMING AND TROUBLESHOOTING THE SYSTEM 65 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 71: ...SECTION 9 TROUBLESHOOTING 67 FIGURE 26 Vacuum pump does not turn on ...
Page 75: ...SECTION 9 TROUBLESHOOTING 71 FIGURE 31 Burner troubleshooting in manual mode ...
Page 77: ...SECTION 9 TROUBLESHOOTING 73 After 45 second prepurge burners do not light continued ...
Page 81: ...SECTION 9 TROUBLESHOOTING 77 FIGURE 36 Air Pressure Switch alarm ...
Page 83: ...SECTION 9 TROUBLESHOOTING 79 FIGURE 38 Repeater troubleshooting ...
Page 85: ...SECTION 9 TROUBLESHOOTING 81 BACnet MS TP troubleshooting continued ...
Page 109: ...SECTION 13 TOUCHSCREEN TREE 105 Touchscreen Tree Overview continued ...
Page 111: ...SECTION 13 TOUCHSCREEN TREE 107 FIGURE 47 Maintenance Unit FIGURE 48 Alarms ...
Page 113: ...SECTION 13 TOUCHSCREEN TREE 109 FIGURE 51 Configuration Zones FIGURE 52 Configuration Unit ...
Page 115: ...SECTION 13 TOUCHSCREEN TREE 111 FIGURE 55 Touchscreen System FIGURE 56 Touchscreen Setup ...
Page 118: ...ROBERTS GORDON CORAYVAC MODULATING HEATING CONTROL CONTROLLER INSTALLATION MANUAL 114 ...