CRVSF-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
32 of 83
FIGURE 17: Condensate Neutralization Tube
10.2 General Ventin
g
Re
q
uirements Model EP-
100, EP-200 and EP-300 Series Pumps
This heater m
u
st be
v
ented in accordance
w
ith the
r
u
les contained in this man
u
al and
w
ith the follo
w
ing
national codes and any state, pro
v
incial or local
codes
w
hich may apply:
United States:
Refer to National F
u
el Gas Code
NFPA 54/ANSI Z223.1 - latest re
v
ision.
Canada:
Refer to Nat
u
ral Gas and Propane
Installation Code CSA B149.1 - latest re
v
ision.
Any portion of
v
ent pipe passing thro
u
gh a
comb
u
stible
w
all m
u
st ha
v
e an appro
v
ed thimble
to conform
w
ith the abo
v
e listed codes.
Vent pipe m
u
st be sloped do
w
n
w
ard a
w
ay from the
p
u
mp ¼'' e
v
ery 10' (3 m).
The bottom of the
v
ent or air intake terminal shall not
be located less than 1
'
(0.3 m) abo
v
e grade le
v
el.
The
v
ent shall not terminate less than 7
'
(2.1 m)
abo
v
e grade
w
here located adjacent to p
u
blic
w
alk
w
ays.
Vent terminal m
u
st be installed at a height s
u
fficient
to pre
v
ent blockage by sno
w
, and b
u
ilding materials
protected from degradation by fl
u
e gases.
Sec
u
re all joints
w
ith #8 x 3/8 sheet metal scre
w
s.
Seal all joints
w
ith high temperat
u
re silicone sealant.
Vent terminal m
u
st be beyond any comb
u
stible
o
v
erhang.
10.2.1 United States Re
q
uirements
Vent m
u
st terminate at least 3
'
(0.9 m) abo
v
e any
forced air inlet located
w
ithin 10
'
(3.1 m).
Vent m
u
st terminate at least 4
'
(1.2 m) belo
w
,
4
'
(1.2 m) horizontally from, or 1
'
(0.3 m) abo
v
e any
door, operable
w
indo
w
, or gra
v
ity air inlet into any
b
u
ilding.
10.2.2 Canadian Re
q
uirements
The
v
ent shall not terminate
w
ithin 6
'
(1.8 m) of a
mechanical air s
u
pply inlet to any b
u
ilding.
The
v
ent shall not terminate
w
ithin 3
'
(0.9 m) of a
Calculated
g
al/h Description
Part Number
Less than 2
Condensate Ne
u
tralization T
u
be 200
01327002
Less than 6
Condensate Ne
u
tralization T
u
be 600
01327003
Less than 10
Condensate Ne
u
tralization T
u
be 1000
01327004
Less than 20
Condensate Ne
u
tralization T
u
be 2000
01327005
Summary of Contents for CorayVac Classic SF Series
Page 2: ......
Page 4: ......
Page 6: ......
Page 65: ...SECTION 14 STARTING THE SYSTEM 59 of 83 FIGURE 41 Vacuum Reading ...
Page 75: ...SECTION18 TROUBLESHOOTING 69 of 83 18 1 Troubleshooting Flow Chart ...
Page 76: ...CRVSF SERIES INSTALLATION OPERATION AND SERVICE MANUAL 70 of 83 Troubleshooting Flow Chart ...
Page 84: ...CRVSF SERIES INSTALLATION OPERATION AND SERVICE MANUAL 78 of 83 ...
Page 88: ...CRVSF SERIES INSTALLATION OPERATION AND SERVICE MANUAL 82 of 83 ...
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......