Installation Manual

Issue 1

Combi Konverter Solar System

Summary of Contents for Combi Konverter Solar System

Page 1: ...Installation Manual Issue 1 Combi Konverter Solar System...

Page 2: ...peration are as follows The system is shown schematically by Figs 1 and 2 using the high output domestic hot water output of the combi to charge up the top of the solar cylinder should insufficient so...

Page 3: ...ing in mind the likely position of the solar panels then an upstairs position will probably be favourite If the combi boiler was retrofitted to replace an old vented hot water storage system then a su...

Page 4: ...on for these devices Connections and Pipe work Where the combi boiler and the cylinder are in fairly close proximity with less than 5 metres of total flow plus return pipe run then 15 mm copper will n...

Page 5: ...gulated as part of the commissioning process In circumstances where the combi is sited at a higher level than the cylinder then a non return valve should be fitted to the hot outlet where it exits the...

Page 6: ...ponents and x22x22mm Tee cylinder connection see fig 6 and now connect the 22mm pipe laid earlier as instructed in connections and pipe work to the spare tapping on this Tee This pipe will be referred...

Page 7: ...ays be sited with the motor spindle horizontal Care should be taken to ensure there is a minimum hydraulic restriction on the inlet side of the pump as this could cause a significantly reduced pressur...

Page 8: ...nder The system should be fitted with an isolating switch to disable the feed to the circulating pump a timer is also supplied this should be fitted in an area accesible to the end user Care should be...

Page 9: ...e pump speed should be set at either speed 2 or 3 but a certain amount of fine tuning may be required to suit the particular installation The temperature setting for the combi circulation pump is achi...

Page 10: ...U and TSTL are the relevant ones When testing the system is operating correctly sensor TSTU on the controller display S3 fig 4 should gradually raise to 55 0 oC whilst the bronze pump and Combi boiler...

Page 11: ...oller It should be explained to the householder that in situations where low levels of solar input coincide with a high hot water demand such as bath filling the hot water delivery characteristics wil...

Page 12: ...RM Solar Ltd Unit 4 Gilcar Way Wakefield Europort Castleford WF10 5QS Tel 01924 224282 Fax 01924 224283 Web www rmsolar com...