T3A Transmitter • 31
Unit Information
The unit information screen allows the end-user to view the following information:
•
The date of manufacture of the sensor assembly.
•
The serial number of the sensor assembly.
This screen is for informational purposes only.
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Unit Information screen appears.
3. Review the information displayed.
4. Press and release the MENU button to move through the Product Settings and
Configuration menu or to exit to the normal operating mode screen.
Latching and Auto Resetting Relay Settings
Relay 1 and Relay 2 can be set to latching or auto resetting. Relays set to auto resetting will
automatically deactivate when the detected gas level falls below the corresponding alarm
setting. Conversely, latching relays, once activated, MUST be manually reset at the device,
regardless of the change in gas detection level readings.
The factory default settings for Relay 1 and Relay 2 are auto resetting. During installation and
setup, Relay 1 and Relay 2 are commonly customized as the following:
Relay 1: Latching/Auto Reset Setting
1. If necessary, enter the Product Settings and Configuration menu by pressing and holding
the MENU button for 6 seconds.
2. Press and release the MENU button until the Relay 1 Latching/Auto Resetting screen
appears.
Common Relay 1 and Relay 2 Settings
Relay
Alarm Setting
Latching/Auto Reset
Relay 1
Alarm 1
Auto Reset
Relay 2
Alarm 2
Latching