
T3A Transmitter • 13
Installation
This section describes procedures to mount the T3A in the monitoring environment and wire
the T3A.
Mounting the T3A
1. Consider the following when you select the mounting site.
•
Select a site where the T3A is not likely to be bumped or disturbed. Make sure there is
sufficient room to perform start-up, maintenance, and calibration procedures.
•
Select a site that is representative of the monitoring environment and where the target
gas is likely to accumulate or where it is most likely to leak. The T3A should not be
installed near an entrance, air intake, or exhaust point.
•
The sensor must point down.
•
Avoid installing the T3A in a location where airborne particles could cover or coat the
sensor.
NOTE:
These guidelines are
ONLY
intended as a general directive for the placement of the
T3A. This information should
NOT
serve as a complete list when considering all
potential parameters for the proper location of the unit. It is
STRONGLY
advised
that a third party Certified Industrial Hygienist, or other Certified Safety Professional,
conduct a site survey and annotate the location and quantity of detection devices that
should be installed for
EVERY
installation of
EVERY
site.
2. Select a mounting location and installation hardware. Mounting to a concrete or steel
structure is recommended to minimize vibration and moisture. Use a maximum 1/4”-20
bolt or 1/4” diameter screw, flat washers, Grade 5 material, and corrosion protection like
paint, galvanization, or zinc plating.