20 • 35-3010RK-04 Sample-Draw Detector
2.
Reconnect the incoming sample line.
3.
Wait 1 to 2 minutes to allow the calibration gas to be drawn out and the reading to
stabilize.
4.
Close the housing door.
5.
Store the components of the calibration kit in a safe and convenient place.
Parts List
Table 4 lists replacement parts and accessories for the sample draw gas detector.
Table 2: Parts List
Part Number
Description
06-1248RK
Sample tubing, 3/16 x 5/16, specify length, (for calibration kit)
07-0034RK
Sealing gasket for CO flow block cavity
30-0610RK
Pump
33-0171RK
Hydrophobic filter (AcroPak)
33-6095RK
Charcoal filter, CF-188
81-0076RK-01
Zero air calibration cylinder (34 liter)
81-0090RK-01
3-gas calibration gas cylinder, 50% LEL methane/12% oxygen/50
ppm CO, 34 liters
81-0155RK
Regulator, demand flow, for 17 and 34 liter steel cylinders
ES-1531-CO
CO sensor
NC-6245
Combustible sensor