RKC INSTRUMENT Z-TIO PLC Communication Quick Instruction Manual Download Page 1

 

 

 

 

Module Type Controller SRZ

 

 

 

IMS01T11-E2

 

Thank you for purchasing this RKC product. In order to achieve maximum performance 
and ensure proper operation of your new instrument, carefully read all the instructions in 
this manual. Please place this manual in a convenient location for easy reference. 

 

1. OUTLINE 

Using the setting examples below, this section explains the configuration when two Z-TIO-C 
or Z-TIO-D temperature control modules (supporting PLC communication) are connected to 
a MITSUBISHI MELSEC Series programmable controller (PLC). 
The PLC communication environmental settings are required to communicate with the PLC. 
The PLC communication environmental settings are set by the host communication or 
loader communication, so the host computer and Z-TIO-C or Z-TIO-D module must be 
connected. (This manual is the explanation by the loader communication.) 

 

Z-TIO-C or 
Z-TIO-D module 

PLC communication RS-485A 

Personal computer 

[PLC setting example] 

Power supply 24 V DC 

MITSUBISHI 

Programmable controller (PLC) 

USB communication converter 
COM-K (RKC product)

 

Loader communication 

 

The Loader port is only for 

parameter setup. 

 

For the host communication, the installation, the detail handling procedures and various 
function settings, please read if necessary the following separate manuals. 

• 

Z-TIO Instruction Manual [for PLC Communication] (IMS01T10-E ):  

  

Enclosed 

with 

Z-TIO 

• 

Z-TIO PLC Communication Quick Instruction Manual [Part 2: Operation] (IMS01T12-E ): 

  

Enclosed 

with 

Z-TIO 

• 

SRZ Instruction Manual [For PLC communication] (IMS01T13-E ): 

   

Separate (Download or sold separately) 

• 

SRZ Instruction Manual (IMS01T04-E ):  Separate (Download or sold separately)

 

 

The above manuals can be downloaded from our website: 

URL: http://www.rkcinst.com/english/manual_load.htm 

 

2. HANDLING PROCEDURES 

 

 Communication program 

preparation 

 Communication port setting 

 Connection of loader 

communication 

See 

6. PLC COMMUNICATION SETTING VIA 

LOADER COMMUNICATION

 

Mounting and Wiring 

PLC communication 

environment setting 

Communication setting 

of Z-TIO module

 

Initial setting 

Data setting

 

See 

3. COMMUNICATION SETTING OF Z-TIO MODULE

 

Mount the Z-TIO-C or Z-TIO-D modules and   
connect the input/output and power supply wiring. 
See 

Z-TIO Instruction Manual   

[for PLC Communication] (IMS01T10-E )

 

See 

6. PLC COMMUNICATION SETTING VIA 

LOADER COMMUNICATION

 

See 

5. CONNECTION TO PLC

 

Connection to PLC 

See

 Z-TIO PLC Communication Quick Instruction   

Manual [PART2: Operation] (IMS01T12-E )

 

PLC setting 

See 

4. PLC COMMUNICATION SETTING

 

See

 Z-TIO PLC Communication Quick Instruction 

Manual [PART2: Operation] (IMS01T12-E )

 

 

3. COMMUNICATION SETTING OF Z-TIO MODULE 

Set communication setting before mounting and wiring of the Z-TIO module. 

 
 

Do not separate the module mainframe from the base with the power turned on. If 
so, instrument failure may result.

 

 

3.1 Module Address Setting 

Set an address for the Z-TIO-C or Z-TIO-D module using a small blade screwdriver. 

• 

When one module is used, set the module address to 0. 

• 

When multiple modules are used, be sure to set one of the modules to module address 0. 
The module with module address 0 will be the master module.

 

 

Address setting switch 

Setting range: 

0 to F [0 to 15: Decimal] 

Factory set value: 0 

Setting of address

setting switch 

1

Z-TIO-C/D module 1 

Z-TIO-C/D module 2

 

 

• 

To avoid problems or malfunction, do not duplicate an address on the 
same communication line. 

• 

For Modbus, the value obtained by adding “1” to the set address 
corresponds to the address used for the actual program.

 

 

3.2 Protocol Selections and   
 

Communication Speed Setting 

Use the DIP switch on the right side of module to select communication speed, data bit 
configuration and protocol. The data changes become valid when the power is turned on 
again or when changed to RUN/STOP. 

 

DIP switch 

ON

OFF

1
2
34

56

7
8

ON

Module main 
frame 

Z-TIO-C/D

 

right side view 

 

(The above figure is for the terminal type. However, the switch positions are the same for the connector type.) 

 

• 

Switch No. 8 must be always OFF. Do not set to ON. 

• 

When two or more Z-TIO-C or Z-TIO-D modules are connected on the same 
communication line, the DIP switch settings of all modules must be the 
same. 

For communication settings when connected to a different functional module, see 
the 

SRZ Instruction Manual [For PLC communication] (IMS01T13-E )

.  

Set the DIP switch settings to the same values as the connected PLC. 

 

Communication speed 

OFF

OFF 4800 

bps 

ON OFF 

9600 

bps 

OFF

ON 19200 

bps 

ON ON 

38400 

bps 

Factory set value

:

 19200 bps 

 

Data bit configuration 

OFF

OFF 

OFF 

Data 7-bit, without parity, Stop 1-bit  * 

OFF

ON 

OFF 

Data 7-bit, Even parity, Stop 1-bit 

ON 

ON 

OFF 

Data 7-bit, Odd parity, Stop 1-bit   

OFF

OFF 

ON 

Data 8-bit, without parity, Stop 1-bit 

OFF

ON 

ON 

Data 8-bit, Even parity, Stop 1-bit 

ON 

ON 

ON 

Data 8-bit, Odd parity, Stop 1-bit 

Factory set value: Data 8-bit, without parity, Stop 1-bit 
* When the Modbus communication protocol is selected, this setting becomes invalid.

 

 

Communication protocol 

OFF

OFF RKC 

communication 

ON OFF 

Modbus 

OFF

ON 

MITSUBISHI MELSEC series special protocol (type 4) 
A compatible, 1C frame, AnA/AnU CPU common command (QR/QW)
QnA compatible, 3C frame, command (0401/1401) ZR register only 
(AnA/AnU/QnA/Q series) 

ON 

ON 

MITSUBISHI MELSEC series special protocol (type 4) 
A compatible, 1C frame, ACPU common command (WR/WW) 
(A series, FX2N

FX2NC series, FX3U/FX3UC series) 

Factory set value: Factory set value varies depending on the instrument specification.   

4. PLC COMMUNICATION SETTING 

Sets the communication items of PLC side. (Recommend setting example) 

 

The setting item varies depending the PLC. The details of the setting procedure for 
the PLC, see the instruction manual for the PLC being used. 

 

Setting example 

 

PLC MITSUBISHI 

MELSEC series 

Personal computer 

Sequencer Programming Software   
GX Developer (Manufactured by MITSUBISHI)

 

 

 

Item Description 

Protocol 

Type 4 protocol mode 

Station number 

00 

Computer link/multi-drop selection Computer 

link 

Communication rate 

Set the same as Z-TIO-C or Z-TIO-D 

Operation setting 

Independent 

Data bit 

Parity bit 

Without 

Stop bit 

Sum check code 

Provided 

Writing during RUN 

Allowed 

Setting modification 

Allowed 

Termination resistor 

Connect the termination resistor attached 
to the PLC 

 

 

5. CONNECTION TO PLC 

 
 
 
 
 
 

Connect a termination resistor between the communication terminals (No.3 
and No. 4) of the module at the end of the communication line from the host 
computer or PLC. 

The communication cable must be provided by the customer. 

 

 

Terminal configuration and wiring example 

The Z-TIO-C/D module has RS-485 communication terminals for RKC communication, 
Modbus/RTU communication and PLC communication protocol. Communication terminals 
are on the base side. 

 

Communication terminals (RS-485) 



Terminal No.

Signal name 

Send data/Receive data
Send data/Receive data

Signal ground 

T/R (A) 
T/R (B) 

SG 

Symbol 

PLC MITSUBISHI 
MELSEC A, AnA, AnU, QnA 
and Q series 

3

4

5

(Base) 

R1: Termination resistor
 Example: 

120 

 

1/2 W 

For the termination resistor 
of PLC side, see the PLC 
Instruction Manual. 

Communication cable 

Short wire

T/R (A) 

T/R (B)

SG 

SG 

T/R (B)

T/R (A)

SDA 

SG 

SDB 

RDA 

RDB 

 

FG 

 

 

 

 

When preparing a cable of connecting the MITSUBISHI MELSEC series to our 
Z-TIO-C/D module, cross each pair of wires the A and B terminal positions on 
their terminal boards are not symmetrical. 

 

 

 

 

 

Z-TIO-C or Z-TIO-D module 

Z-TIO module 16 

Connected by 
the internal 

communication line

RS-485 

Shielded twisted
pair wire 

Pair wire

SG 5 

T/R (A) 3 

T/R (B)

Up to 16 Z-TIO-C/D modules can be connected. 

R1: Termination resistor 
 (Example: 

120 

  1/2 W) 

SG 5 

T/R (A) 3 

T/R (B)

(

(+) 

(

(+) 

PLC MITSUBISHI 

MELSEC series 

SDA (+) 

SDB (

SG 

RDA (+) 

RDB (

R2

R2: Termination resistor
 (PLC 

side) 

Z-TIO module 1 

For the termination resistor 
of PLC side, see the PLC 
Instruction Manual. 

 

 

 

6. PLC COMMUNICATION ENVIRONMENT 

SETTING VIA LOADER COMMUNICATION 

This section explains how to configure the PLC communication environment settings by 
loader communication.

 

To perform loader communication, a communication program must 

be created. 

 

6.1 Preparation of USB Communication Converter 

To perform loader communication, our converter and a communication cable are required. 

 

USB communication converter COM-K (With USB cable) 

  Loader communication cable W-BV-01 [option] 

 

6.2

 

Preparation of Communication Program

 

Refer to the RKC communication protocol or the Modbus communication protocol to create 
a communication program. 
(However, the loader communication cannot be used when Modbus protocol is selected.) 

 

For RKC communication or Modbus communication protocol, see 

SRZ Instruction 

Manual (IMS01T04-E )

 

6.3 Setting of Loader Communication 

For loader communication, set the communication port of the computer to the following 
values. There are no loader communication settings on the Z-TIO-C/D module side. 
 

Communication setting of the personal computer side 

Communication speed 

38400 bps 

Start bit 

Data bit 

Parity bit 

Without parity 

Stop bit 

Above setting data is fixed. 

 

6.4 Connection of Loader Communication 

Connect a USB communication converter COM-K between the personal computer and the 
Z-TIO-C or Z-TIO-D module. 

 

USB communication 
converter COM-K 

(RKC product) 

Connect to USB 

port of personal 

computer.

 

Connect to USB connector 

of COM-K 

Loader communication
cable (W-BV-01) 

[option] 

Connect to

loader communication 

connecter 

USB cable (Attached to COM-K)

Personal 

computer 

Z-TIO-C or   
Z-TIO-D module

Connect to

loader communication 

connecter of Z-TIO-C/D

module 

The termination 
resistor builtin to 
the COM-K. 

 

When using the loader communication, the address of all SRZ modules is fixed at 0. 
The setting of the address setting switch is disregarded. 

 

All Rights Reserved, Copyright 

 2006, RKC INSTRUMENT INC. 

Z-TIO 

PLC Communication 
Quick Instruction Manual 

[PART1: Preparation]

 

Temperature Control Module 
[for PLC Communication]

 

CAUTION

 

 

 

 

To prevent electric shock or instrument failure, turn off the 
power before connecting or disconnecting the instrument and 

peripheral equipment.   

!

WARNING

Reviews: