INSTALLATION
Installation Instructions for SIS Bus Bar Systems A2MS001EN revision R05
46 / 130
Prohibited Spacing Dimensions
………
NOTICE!
Risk of Material Damage from Incorrect Spacing of
Bus Bars!
Improper installation and incorrect spacing of individual
fixation units can lead to resonant vibrations at certain
intervals within a bus bar due to their natural frequency.
The bus bars may be subjected to very heavy
mechanical stress, and in extreme cases the insulation
may become damaged.
– It is imperative to adhere to the spacing
dimensions between the individual sliding
bearings (Bg), fixed bearings (Bf), and the
fixation units as shown in the installation
drawing.
– If the spacing dimensions cannot be adhered to
for reasons related to the performance of the
installation
or building interferences, any change must be
coordinated with RITZ Instrument Transformers
GmbH beforehand, and noted in the drawings.
4.5.2
TIGHTENING TORQUE
VALUES
Adhere to the tightening torque values as per
Appendix B for stainless steel bolts and nuts.
NOTICE!
Conical spring washers, as per DIN 6796, must not
be re-used after being removed!
4.5.3
FASTENING BUS BAR
ELEMENTS
Personnel:
Installation staff
Protective Equipment:
Occupational safety clothing
Industrial safety helmet
Protective gloves
Safety footwear
1.
Install bus bar elements in the fixation units in
accordance with the installation drawings.
2.
In the process, make sure they are positioned
correctly to each other and with the correct spacing
(see chapter 4.5.1
3.
Lay an earthing bar or earthing cable parallel to
the bus bar system.