Inst
alla
tion
Installation: Assembly, connection and start-up
104
Starting up
Adjusting the operating mode
The switching device has the following operating modes, which can be selected using the operating mode switch:
*
The switch-off warning may shorten the service life of certain illuminants such as fluorescent lamps with conventional ballast.
Operating elements
1. Timer button Z
2. Command setting button P
3. Operating mode switch
4. Yellow LED, function indicator settings
5. Green LED, relay on function indicator
Switch setting
Operating mode
Function
0
OFF/Time setting
Switching device permanently OFF /
Set time mode
1
ON
Switching device permanently ON
2
Current surge
switch
Each switching command switches the switching device on or off
3
Time relay (short
time)
Each switching command switches the switching device on for the short
time that has been set.
4
Time relay (short
time) with
extension
Each switching command switches the switching device on for the short
time that has been set; each switching command that is issued before the
timer runs out resets the timer.
5
Time relay (long
time)
Each switching command switches the switching device on for the long
time that has been set.
6
Time relay (long
time) with
extension
Each switching command switches the switching device on for the long
time that has been set; each switching command that is issued before the
timer runs out resets the timer.
7
Remote switch
The switching device switches on for as long as the connected button is
pressed.
Note:
No TwinBus control is possible in this operating mode.
8*
Time relay (long
time) with
extension, switch-
off warning
Each switching command switches the switching device on for the long
time that has been set; approx. 30 seconds before the time elapses, the
switching device switches off briefly 3x; each switching command that is
issued before the timer runs out resets the timer.
9*
Time relay (long
time) with
extension, switch-
off warning,
continuous light
Each switching command switches the switching device on for the long
time that has been set; approx. 30 seconds before the time elapses, the
switching device switches off briefly 3x; each switching command that is
issued before the timer runs out resets the timer.
Independent of the time set, the switching device is switched on for 60
minutes by three switching commands following one another in rapid
succession.
'&
% $ $ # " "
!
#
"
!
00127-0
Summary of Contents for TWINBUS
Page 2: ...2 ...
Page 41: ...Installation Assembly connection and start up 41 Installation 00042 0 ...
Page 156: ...Installation Installation Assembly connection and start up 156 ...
Page 193: ...Notes 193 ...
Page 194: ...Notes 194 ...
Page 195: ...Notes 195 ...
Page 196: ...Notes 196 ...