Wireless Supervisor Photoelectric Smoke Detector
12
Specifications
Voltage:
6 volt
Typical Average Standby
Current:
0.010mA
Typical Test Current:
55mA
Typical Alarm Current:
55mA
Peak Trouble Pulse Current:
4.73mA
Peak Pulse Current:
0.074mA
Battery Life:
At least 1 year under normal conditions
with Lithium Batteries
Battery Type:
2xCR123 3V Lithium battery
Low Battery Threshold:
5.2 Volt
Low Battery Beep rate:
One beep every 30 seconds
Low Battery Life:
At least 30 days from warning signal
Operating Temperature:
-10°C to 40°C (14°F - 104°F)
Operating Humidity:
10% to 85% RH, no condensation or icing
Color:
White
Dimensions:
Diameter: 148 mm (5.83”)
Height: 53 mm (2”)
Alarm Sound Level:
Exceeds 85dB at 3m (10 feet)
Transmitter Characteristics
:
Nominal Center Frequency
RWT33S86800A and 74015 : 868.65 MHz
RWT33S43300A: 433.92 MHz
Supervision Time
15 min. for 868.65 MHz /
65 min. for 433.92 MHz
In order to continue improving the product, RISCO Group reserves the right to