background image

WS6-M 

ADJUSTABLE END STRIPPER

 

Note:  This tool is a manually operated cutting device for polyethylene, (XLPE)cross link polyethylene, and (EPR) 
ethylene propylene rubber insulation on 15KV to 46KV cables 22.86mm ( .900”) to 52.07mm (2.030”) in diameter.  

 

OPERATING INSTRUCTIONS 

For best results, the end of the cable to be stripped should be cut straight and square using a 
hack-saw or curved jaw cable cutters.  

Step 2.

  (Fig. 2) To insert the bushing into the WS6-M, line up rib 

on the bushing with the slot on the WS6-M housing.  Raise the 
cutting blade by depressing outer end and insert the bushing until it 
locks into place. 

Step 3.

  (Fig. 3) To adjust the stop bar for desired length of 

conductor exposure,  loosen set screw located on the end of 
the tool body directly above the stop bar.  Adjust the stop 
bar  to the desired length of insulation to be stripped and 
tighten the set screw. 

Step 4.

  (Fig. 4) To strip the insulation, insert the cable into the 

WS6-M until it comes in contact with cutting edge of the blade.  
Always check the blade position with respect to the conductor, 
before stripping the insulation.    

Fig. 4

 

Fig. 3 

Fig. 2 

RIB 

SLOT 

PRESS 

CUTTING 

BLADE 

GRADUATED 

STOP BAR 

CABLE 

BLADE CUTTING 

EDGE 

SET SCREW 

 

 

Warning

!

 

This tool is not protected against electrical shock!

  Always use 

OSHA/ANSI

 or other industry approved eye protection 

when using tools.  This tool is not to be used for purposes other than intended.  Please read and understand instructions before using  
this tool. 

Step 1.

 (Fig 1) Check the bushing by sliding it over 

polyethylene insulation (Fig 1A) or semi-con over EPR 
insulation (Fig. 1B). The bushing should fit snugly and 
still rotate easily on the cable. 

We recommend the use of 

lubricant be used on the semi-con over EPR cable.

 

Fig. 1A 

Fig. 1B 

Fig. 1

 

Reviews: