5.4.2. Protocol 2: Ranger B
Character
Number
0
1
2
3
4
5
6
7
8
9
10
Description
S
TX
S
ta
tu
s
S
ign
W
e
igh
t
W
e
igh
t
W
e
igh
t
W
e
igh
t
W
e
igh
t
W
e
igh
t
W
e
igh
t
Units
Character
Number
11
12
13
Description
Units
Units
E
TX
Function
Description
STX
Start of Transmission Character (ASCII 02H).
Sign
Represents the sign of the weight reading (space for positive, dash
(-) for negative.
Weight
These seven characters are a string containing the current weight
including the decimal point. If there is no decimal point, then the
first character is a space.
Examples:
( 300) with a leading space would represent 300 units.
( 3.00) Is another acceptable string.
Status
The status character provides information on the weight reading.
The characters G/N/U/O/M/E represent
Gross/Net/Underload/Overload/Motion/Error, respectively. A
space (ASCII 20H) can also be sent. This character may only
represent one status at any one time.
Units
A three character string, the first character being a space, followed
by the actual units. eg. ( kg) or ( t). If the weight reading is not
stable, the unit string is sent as ( ).
ETX
End of Transmission character (ASCII 03H).
Summary of Contents for D32 series
Page 1: ...D32x XD30 Remote Display Manual D300 601 200...
Page 45: ...Remote Display Installation Manual Software Version 4 x D300 602 202 Page 45 Notes...
Page 46: ...Remote Display Installation Manual Software Version 4 x Page 46 D300 602 202 Notes...
Page 47: ...Remote Display Installation Manual Software Version 4 x D300 602 202 Page 47 Notes...
Page 48: ...Remote Display Installation Manual Software Version 4 x Page 48 D300 602 202...