Installation & Servicing Instructions Rinnai Q Premier
6
WHAT TO DO IF YOU SMELL GAS
- Do NOT try to light any appliance.
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
- If you cannot reach your gas supllier, call the
fi
re department.
Should overheating occur or the gas supply fail to shut off, do not turn off or
disconnect the electrical supply to the pump. Instead, shut off the gas supply
at a location external to the boiler.
Chemicals that are corrosive in nature should not be stored or used near the
boiler or vent termination.
1.5 Follow these instructions for the space heating water
Unsuitable heating system water can cause the formation of scale or sludge, which
affects system ef
fi
ciency. It can also cause corrosion and reduce life of the heat
exchanger.
– You must follow Rinnai guidelines for boiler water quality.
– Thoroughly
fl
ush the system prior to
fi
lling.
– Follow the Rinnai cleaning instructions.
– Never use water that has been treated by a reverse osmosis, D.I., or distilled water
to soften the water to
fi
ll the heating system.
– Do not use inhibitors or other additives unless approved by Rinnai for that purpose.
– When freeze protection of the heating system is desired, only use Rinnai-approved
antifreezes. The allowed maximum concentration is 50%.
– When using oxygen-permeable pipes, e. g. for under
fl
oor heating systems, you
must separate the system from the boiler using plate heat exchangers.
– Valve off boiler while
fl
ushing system, do not introduce any system cleaner into the
boiler loop. Flush system thoroughly to remove all system cleaner before
fi
lling boiler.
Approved
antifreeze:
• Rhomar RhoGard Mutli-Metal (AL safe)
• Sentinel X500
(max. concentration 50%) • Noble Noburst AL
• Fernox Alphi 11
Approved system cleaner:
• Noble Noburst Hydronic System Cleaner
• Fernox F3 Cleaner
•
Rhomar
Hydro-Solv
9100
•
Sentinel
X400
The system cleaners from NoBurst, Rhomar, and Fernox are not to be used in
the boiler. The boiler must be closed off (valved off) from the rest of the system
or not connected while the cleaners are in the system. The system should then
be drained and then thoroughly fl ushed with clean water to remove all the
system cleaner.
Approved inhibitors:
• Rhomar Pro-tek 922
• Sentinel X100
•
Noble
Noburst
AL
inhibitor
See the Rinnai Boiler Applications Manual or Chapter 6 and 10 of this manual for
additional information.
If problems occur when using sanitary water with a chlorine content
higher than 150 mg/l, no recourse can be made to the terms of the limited
warranty.
NOTICE
i
NOTICE
i
!
WARNING
!
WARNING
NOTICE
i