Split AC IM
WARNING
INSTALLATION
This appliance shall be installed in accordance with local electrical safety regulations by an
authorised person such as a licensed electrician.
This appliance is a Type 1 Electrical Appliance.
Make sure the live wire, neutral wire and earth wire in the power socket are properly connected.
Inadequate or incorrect electrical connections may cause fire or electric shock.
The yellow-green wire in air conditioner is the earthing wire which cannot be used for other
purposes. Improper earthing may cause electric shock.
The circuit breaker must have the functions of magnetic tripping and heat tripping to prevent
short circuit and overload.
Use a standard circuit breaker and fuse conforming with the rating of the appliances.
Model
HSNRJ25B
HSNRJ35B
HSNRJ50B
HSNRJ70B
HSNRJ80B
Circuit Breaker (Amps)
16
16
16
20
25
The unit must be earthed in accordance with local regulations.
Connect all wiring tightly. Failure to do so may result in electric shock or product failure.
DO NOT
supply power to the unit until all wiring and tubing are completed.
Select an installation location where the components can be mounted securely and accessible
for service and replacement.
Make sure tubing is properly insulated to ensure optimum performance.
Install the drain hose properly for smooth drainage of condensed water.
Make sure to check for and rectify any refrigerant leaks after you install or repair the unit.
This appliance uses R32 (difluoromethane) refrigerant, which is a flammable gas class 2.2
according to AS/NZS 1677 and must be handled by a refrigeration mechanic with appropriate
Australian refrigerant handling licence.
WARNING
Risk of fire / flammable material. If the refrigerant is leaked, together with an
external ignition source, there is a possibility of ignition.
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS and
INSTALLATION MANUAL before operation.
Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION
MANUAL, and the like.
Certain levels of refrigerant require minimum room sizes. Please ensure that these minimum
room sizes are adhered to for standard installations (up to 10m pipe length). If larger refrigerant
charges than standard are used then please consult AS/NZS 60335.2.40 to determine the safe
minimum floor area for the installation.
Make sure that the area has been made safe by having suitable ventilation and is free from ignition
sources before charging or releasing the charge of R32.
Model
HSNRJ25B
HSNRJ35B
HSNRJ50B
HSNRJ70B
HSNRJ80B
Standard Charge (g)
660
1000
1200
1350
1600
Minimum Floor Area (m
2
)
1.00
1.00
1.74
1.74
2.45
WARNINGS AND IMPORTANT INFORMATION