36
4.5.5 Defrosting cycle
Especially when the unit works when the outside temperature is very low, frost may appear on the evaporator. In this
case the defrost process is activated and the relative LED icon flashes.
4.5.6 Anti-freeze protection
If the unit is switched off but still under voltage, and the tank temperature drops below 5°C; the electric heater is forced
to work until reaching the same temperature at 10°C. In this case the error code “P06” will appear on the display of
the unit.
4.6 PARAMETERS’ CONTROL AND SETTING
The parameters can be displayed on the screen. Certain user/installer parameters can be changed directly, while the
others can be displayed but only authorized technicians can access with password to to modify them. Below is given
the list of the parameters.
Once the parameters have been set by the installer, it is not recommended for the user to modify
them. Please contact a qualified person for modifying the setting values of the parameters.
Parameter nr. Description
Range
Default
Notes
A
Lower tank temperature sensor
-20 ~ 99°C
In case of lower tank temp. sensor failure, the error code
“P01” will be displayed.
B
Upper tank temperature sensor
-20 ~ 99°C
In case of upper tank temp. sensor failure, the error code
“P02” will be displayed.
C
Evaporation temperature sensor
-20 ~ 99°C
In case of evaporation temp. sensor failure, the error code
“P03” will be displayed.
D
Compressor suction temperature sensor
-20 ~ 99°C
In case of compressor suction temperature sensor failure,
the error code “P04” will be displayed.
E
Room temperature sensor
-20 ~ 99°C
In case of room temperature sensor failure, the error code
“P05” will be displayed.
F
EXV open steps
100 ~ 470 step
Not adjustable.
01
ΔT compared to the compressor restart setting
temperature.
2 ~ 15°C
5°C
Adjustable
02
Reserved
03
Reserved
04
Weekly disinfection temperature
50 ~ 70°C
70°C
Only technician of “TAC” can change it.
05
Holding time of the disinfection temperature
0 ~ 90 min
30 min
Only technician of “TAC” can change it.
06
Defrosting cycle time duration
30~90 min
45 min
Only technician of “TAC” can change it.
07
Outside temperature of defrost cycle
initialization
-30 ~ 0°C
-7°C
Only technician of “TAC” can change it.
08
Defrosting termination temperature
2 ~ 30°C
20°C
Only technician of “TAC” can change it.
09
Maximum defrosting cycle time
1 ~ 12 min
8 min
Only technician of “TAC” can change it.
10
Operating mode of the electronic expansion
valve.
0 (auto)
1 (manual)
0
Only technician of “TAC” can change it.
11
Superheat setting value
-9 ~ 9°C
5°C
Only technician of “TAC” can change it.
12
Steps for manual adjustment of the electronic
expansion valve
10 ~ 47 step
35 step
Only technician of “TAC” can change it (N*10)
13
Time to start a disinfection cycle
0~23
23
Adjustable (hours)
14
ΔT for electric heater initialization
2 ~ 20°C
7°C
Adjustable
15
Compressor cumulative operation Time
10 ~ 80 min
30 min
Only technician of “TAC” can change it.
16
Increase of the lower tank temperature
0 ~ 20°C
2°C
Only technician of “TAC” can change it.
17
ON/OFF
0 (From remote
signal)
1 (from
photovoltaic
system)
0
Adjustable
18
Room temperature update period.
2 – 120 min
15 min
Adjustable
19
Compensation temperature for the climatic
curve.
-10 – 10 °C
0 °C
Adjustable
20
Type of temperature set control.
0 (set by TS1) –
1 (65°C)
0
Adjustable
Summary of Contents for EHP-WH110
Page 6: ......
Page 7: ...7 1 INTRODUCTION...
Page 13: ...13 2 OVERVIEW OF THE UNIT...
Page 19: ...19 3 INSTALLATION...
Page 28: ...28...
Page 29: ...29 4 APPLIANCE OPERATION...
Page 38: ...38...
Page 39: ...39 5 MAINTENANCE...
Page 42: ...42...
Page 43: ...43 6 TECHNICAL INFORMATIONS...
Page 46: ...46 6 3 WIRING DIAGRAM Please refer to the wiring diagram sticked on the electric box...