Compact 2 Installation Guide: 11817-D 04-15
|
5
Enclosure dimensions
The main points governing location are flueing and warm air distribution. The
enclosure dimensions provided are critical to the installation of this appliance and
must be adhered to.
The heater must be positioned on a flat level surface that allows free movement of
the appliance.
Inbuilt masonry installations
Inbuilt mock chimney installations
Inbuilt masonry
W-width
595-700 mm
H-height
550-630 mm
D-depth
360 mm*
Use a slurry of sand and cement to level the
base as required.
* Minimum clearance required from the spigot to the back
of the fireplace is 50 mm (p. 12).
Inbuilt mock chimney
W-width
685 mm
H-height
615 mm
D-depth
380 mm
The zero clearance box needs to be supported
within the enclosure. Either construct a base
using board with supporting joists or support
with the frame itself—must be capable of
supporting a minimum of 1.5 times the weight
of the appliance.
When preparing a cavity/frame for a zero
clearance installation, the total cavity depth
MUST include the thickness of the external
cladding as the zero clearance box MUST BE
installed flush with the cladding surface, to
ensure alignment of the flue.