Linear smoke detector «IPDL-Ex» (hereinafter, the IPDL-Ex) refers to intrinsically 

safe electric equipment with «ia» level «intrinsically safe electric circuit» explosion 
protection. IPDL-Ex is intended for detecting ignitions accompanied with smoke 
in the protected hazardous premise, generating an alarm message by relay 
contacts closing and transmitting the message to zone extension module BRSS-Ex 
(hereinafter, the BRSS-Ex).

2 Features of the IPDL-Ex

- The intrinsically safe parameters of the IPDL-Ex match those of BRSS-Ex.
- Detects combustion products in a monitored zone created by an optical beam 

between the infrared radiation transmitter and receiver.

- Generates «Fire» alarm messages if threshold concentration of combustion 

products level is exceeded;

- Generates «Fault» messages in case of service trouble;
- Transmits «Fire» and «Fault» alarm messages via alarm loops AL1 and AL2 

correspondently;

- Diagnoses faults and transmits the results to an optical alarm external device 

(hereinafter, OAED).

3 Specifications

3.1 IPDL-Ex intrinsically safe electric circuits have the following valid parameters:
- maximum input voltage (U

i

) – 16 V;

- maximum input current (I

i

) – 150 mA;

- maximum internal capacitance (С

i

) – 1000 pF;

- maximum internal inductance (L

i

) – 0.01 mH.

3.2 IPDL-Ex operation threshold (intensity reduction of a beam passed through 

the monitored environment, at which IPDL-Ex generates a «Fire» message) fall 

inside the limits of 20 % … 50 %.

3.3 The time period during which IPDL-Ex generates a «Fire» alarm message, 

with ambient optical density increasing at the rate of (0.52 ± 0.05) dB/s does not 
exceed 10 s. 

3.4 IPDL-Ex generates three types of messages:

Table 1

Message

Al1 (Fire) 

Relay 

Contacts

Al2 (Fault) Relay Contacts

Transmitting Module (TM) 

LED Indicator and

 OAED LED Indicator

DIР «2»

RM - «ОN»

DIР «2» 

RM - «ОFF»

«Norm» 

«Fire»

«Fault»

Open 

Closed

-

Open

-

Closed

Closed

-

Open

Blinking at freq. 0.25 Hz 

Continuous lighting 

Blinking at freq. 1 Hz

3.5 IPDL-Ex remains in a standby mode in case the transmitter radiation is 

interrupted for the time period less than 1 s.

3.6 The positioner adjusts the optical beam level tilt. Permissible vertical tilt 

angle of the optical beam is not less than ±5°, tilt angle in horizontal plane is not 
less than ±10°.

3.7 Permissible optical path length is 8 to 150 m.
3.8 Structurally, IPDL-Ex consists of a transmitting module (hereinafter, the TM) 

generating a directed infrared radiation flow and a receiving module (hereinafter, 
the RM) receiving the radiation and generating an output signal.

3.9 The maximum current consumption of IPDL-Ex TM is 10 mA. The maximum 

current consumption of IPDL-Ex RM is:

a) 10 mA in a standby mode;
b) 20 mA in «Fault» and «Fire» modes.
3.10 The IPDL-Ex provides IP41 rating.
3.11 Dimensions of IPDL-Ex TM and RM – 120 x 120 x 80 mm.
3.12 IPDL-Ex weight – maximum 0.8 kg.
3.13 IPDL-Ex ensures safe operation at:
- ambient temperature from minus 25 to +55 °С;
- relative air humidity 93 % at an ambient tempe40 °С.
- background natural and/or artificial illumination with of 12 000 lx or more 

intensity.

- DC voltage variations at power supply terminals within the range from 8 to 14 V.
-  impact of sinusoidal vibration with acceleration of 0.5 g within the frequency 

range 10 ... 150 Hz;

- impact of the straight mechanical blow delivered with the energy 1.9 J.

4 Scope of Delivery

Each IPDL-Ex unit package contains items listed in Table 2.
Table 2

Name

QNT

Linear smoke detector «IPDL-Ex»:
Transmitting module 
Receiving module
Optical alarm external device
Screw 3-3х40.016 
Wall plug NAT 5х25 SORMAT
Linear smoke detector «IPDL-Ex». Installation Guide

1 pc.
1 pc.

1 pc.*
4 pcs.
4 pcs.

1 copy

*) supplied optionally

LINEAR SMOKE DETECTOR

«IPDL-Ex»

Installation Guide

Figure 1

5.1 The principal structural elements of the transmitting module (TM) and the 

receiving module (RM) (See Figure 1) are as follows: 1 – base with a positioner 
mirror; 2 – case; 3 – optical unit with an adjuster; cover with a light filter (not shown).

5.2 The bases of the TM and the RM have openings for fastening on the place 

of installation by means of screws.

5.3 The base of the RM comprises openings for a HL1 LED indicator, entries 

for power cables, AL and optical alarm external device OAED.

5.4 The cover is fastened to the base with the help of a latch.
5.5 The TM includes case, PCB and TM optical unit.
5.6 The following elements are installed on the TM PCB:
- a transmitter installed in the focus of the TM optical unit;
- DIP-switch 1, 2 of transmission power level as per Table 3;
Table 3

Distance between the TM and the RM, m

RM «P» Switch Arms Positions

150

60

20

1 - ON, 2 - ОFF

1 - ОFF, 2 - ОN

1 - ОFF, 2 - ОFF

- a terminal block «+U-

»

 for power supply connection;

- a terminal block and a «TEST

»

 key button intended for self-test mode 

engagement.

5.7 The RM includes:
- case;
- the PCB installed on the base in the focal plate of the RM optical unit ensures 

analog and digital signal processing, external circuits switching, provides information 
display at OAED;

- the RM optical unit. 
5.8 The following elements are installed in the RM circuit board:
- «+Un-

»

 terminal block for power supply connection;

- «Al1» and «Al2» terminal blocks for connecting AL1 (Fire) and AL2 (Fault) 

alarm loops;

- «+K-

»

 terminal block for connecting an external optical device (ED) in a standby 

mode or a voltmeter for signal level measurement during adjustment;

- «A

»

 DIP-switch 1 in the ON position changes the RM to an adjustment mode;

- «P

»

 DIP-switch 2 determines the polarity of AL2 signal (Fault):

1) ON – AL2 normally opened contact;
2) OFF – normally closed AL2 contact; 
- operating threshold adjustment is carried out by means of DIP-switches 3, 4 

«THRESHOLD

»

 in compliance with Table 4.

- RM LED indicator HL1 of RM displays the current status of IPDL-Ex («Norm», 

«Fire», «Fault») and indicates the delivery or non-delivery of a signal in an adjustment 
mode; 

- HL2 – HL5 LEDs display signal level in an adjustment mode.
Table 4

«THRESHOLD» (% of Signal Strength 

Loss as Compared to the Set Level)

«THRESHOLD»

Position of  

DIP-switch 3

«THRESHOLD»

Position of  

DIP-switch 4

20

30

40

50

OFF

OFF

ON

ON

OFF

ON

OFF

ON

6 IPDL-Ex Installation

6.1  Safety  Rules  for  Operation  of  Customers’  Electrical  Installations  and 

Customers’ Electrical Installations Operation Rules, the recommendations of local 

fire department should be observed to in the process of IPDL-Ex installation and 
operation.

6.2 The IPDL-Ex should be installed in closed or semi-closed premises at most 

probable smoke accumulation points in case of a fire (above fire hazard locations, 
far away from exhaust ventilation and air draughts).

6.3 The bases for the TM and the RM installation should be rigid and should 

have level surfaces (a load-bearing wall or a timber).

6.4 The IPDL-Ex should be installed at the location accessible for maintenance 

in line-of-sight zone on a side of the premise passages.

6.5 The distance between the TM and the RM must not exceed 150 m, whereupon 

there should be no overcovering objects in the monitored zone and the possibility 
of their emergence should be excluded.

5 Design of the IPDL-Ex

Transmitting module

Receiving module 

1 – base;
2 – optical unit; 
3 – printed circuit board (PCB);
4 – adjustment screw in vertical 
plane; 
5 – adjustment screw in 
horisontal plane;
6 – mirror;
7 –  visor.

AL1

A

TEST

AL2

P

THRESHOLD