Technical description of the burner
4.3
Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1,013 mbar - Altitude 0 m a.s.l.
(2)
Input valve gas pressure with zero pressure in the combustion chamber and at maximum burner output.
(*)
To operate with LPG just a different adjustment of the gas valve is required.
4.4
Electrical data
Tab. B
NOTE:
It is important to protect the burner with an external fuse
(see wiring diagrams) to prevent the control getting dam-
aged. The control box does not have a replaceable internal
fuse.
Model
RX 150 S/PV
Type
904T4
Head assembly
Supplied with head assembled
Power
(1)
Delivery
(1)
min - max
min - max
kW
Mcal/h
25-145
21.5-124.7
Fuels
Natural gas: G20 (methane), G25 - LPG: (G31)
(*)
Supply pressure
(2)
mbar
10-30
Gas valve input diameter
3
/
4
”
Operation
–
Intermittent (min. 1 stop in 24 hours)
–
Modulating
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 55
Burner weight (without packaging)
kg
9
Model
RX 150 S/PV
Type
-
Auxiliary circuit electrical supply
1N ~ 230V +/-10% 50/60 Hz
Electrical supply
1N ~ 230V +/-10% 50/60 Hz
Fan motor
rpm
V
kW
A
8400
230 V 50/60 Hz
0.24
1.8
Ignition transformer
V1 - V2
I1 - I2
230 V - 2 x 10 kV
0.3 A - 50/60 Hz 40 mA
Absorbed electric power
kW max
0,34
Protection level
IP 20
Summary of Contents for RX 150 S/PV
Page 2: ...Translation of the original instructions...
Page 48: ...20151674 46 GB Appendix Electrical panel layout 0 1 0 0 1 0 RX 150 S PV...
Page 49: ...47 20151674 GB Appendix Electrical panel layout...
Page 50: ...20151674 48 GB Appendix Electrical panel layout...
Page 51: ...49 20151674 GB Appendix Electrical panel layout 0 0 0 1 1...
Page 54: ......
Page 55: ......