Technical description of the burner
4.6
Maximum dimensions
The dimensions of the burner are given in Fig. 1.
Bear in mind that inspection of the combustion head requires the
burner to be opened and the rear part drawn back on the slide
bars.
The maximum dimensions of the open burner are indicated by
the value I.
Tab. E
(1) Blast tube: short-long
4.7
Firing rates
The
maximum output
is to be chosen within area A of the
diagram (Fig. 2).
The
minimum output
must not be lower than the minimum limit
of the diagram.
Fig. 1
D1702
mm
A
B
C
D
E
F
(1)
G
H
I
(1)
L
M
N
O
RS 200/M BLU
732
427
329
573
863
373-503
221
430
1442-1587
228
141
261
Rp2
CAUTION
Model firing rate (Fig. 2) refers to operation on
G20 - G25.
If using G31, the minimum output goes from 550
to 630 kW.
ATTENTION
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
shown on page 21.
-2
Mcal/h
kW
0
2
4
6
8
10
12
14
A
2400
2100
2200
1400 1600 1800 2000
1000 1200
800
600
1900
1700
1500
1300
1100
900
700
500
D9599
Thermal power
Pressure in the chamber
chamber -
mb
ar
Fig. 2