20160778
6
GB
Technical description of the burner
3.1
Burner models designation
Tab. A
3.2
Technical data
Tab. B
(1)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 16)(Fig. 4, page 12) with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
3
Technical description of the burner
Model
Riello Code
RBNA Code
Voltage
Flame safeguard
RS 70/M TC FS1
20160208
20166044
208-230/3/60
Burner mounted
20166045
460/3/60
20160227
20166046
575/3/60
RS 100/M TC FS1
20160233
20166047
208-230/3/60
Burner mounted
20166048
460/3/60
20160238
20166049
575/3/60
RS 130/M TC FS1
20160253
20166101
208-230/3/60
Burner mounted
20166102
460/3/60
20160256
20166103
575/3/60
Model
RS 70/M
RS 100/M
RS 130/M
Output
(1)
High
MBtu/hr
kW
1761 - 3084
516 - 904
2644 - 4405
775 - 1291
3521 - 5545
1032 - 1625
Low
MBtu/hr
kW
512
150
570
167
607
178
Fuel
Natural or propane gas
- Max. delivery
SCFH
3084
4405
5545
- Pressure at max. delivery
(2)
“WC
4.06
3.66
3.20
Operation
Low - High or modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °c)
Combustion air temperature
°F max
140 (60 °c)
Noise levels
(3)
dB(A)
75
77
78.5
Weight (complete with packaging)
lbs
154
161
168