Installation
5.11
Combustion head setting
In addition to varying air flow depending on the output requested,
the air gate valve servomotor 4) (Fig. 5) by means of a lifting as-
sembly - varies the setting of the combustion head.
This system allows an optimal setting even at a minimum firing
rate.
For the same servomotor rotation, combustion head opening
can be varied by moving the tie rod onto holes 1-2-3) (Fig. 17).
The choice of the hole (1-2-3) to be used is decided on the basis
of diagram (Fig. 19) against the required maximum output.
Setting is pre-arranged in the plant for the maximum run (hole 3,
Fig. 17).
If combustion requirements require you to move spacer 1)
(Fig. 18) onto the 1st or 2nd hole of the gear and, at the same
time, the hinge is on the right, you need to fit the spacers 4)
(Fig. 18) supplied with the burner.
Proceed as follows (Fig. 18):
unscrew nuts 2), remove tie rod 3);
unscrew spacer 1) and position it on the hole you want;
screw the spacers (4) onto spacer (1) and screw (5) respec-
tively;
Refit the tie rod and nuts.
Fig. 17
0
1
2
3
4
6
3
2
1
4
D3093
D3409
Fig. 18
Fig. 19
3
2
1
0
2400 2800 3200 3600 4000 4400 4800 5200
1200 1600 2000
800
5600 6000
6800 7200
6400
D10533
N° holes
Max burner output -
kW
Summary of Contents for RLS 650/E MX
Page 2: ...Translation of the original instructions ...
Page 44: ...20027766 42 GB Appendix Electrical panel layout ...
Page 45: ...43 20027766 GB Appendix Electrical panel layout ...
Page 47: ...45 20027766 GB Appendix Electrical panel layout ...
Page 48: ...20027766 46 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 49: ...47 20027766 GB Appendix Electrical panel layout 0 ...
Page 50: ...20027766 48 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...