25
20182250
GB
Installation
5.11
Nozzle installation
The burner complies with the emission requirements of the EN
267 standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by the Manufacturer in the In-
struction and warning booklet should be used.
Fit the nozzle with a pipe wrench (24 mm), passing through the
central opening of the flame stability disc (Fig. 21).
Fit the nozzles on the nozzle holder without the fuel interception
rod.
To calibrate the flow rate range within which the nozzle should
operate, adjust the fuel pressure on the nozzle return line, ac-
cording to and Tab. M.
5.11.1 Recommended nozzle
•
Fluidics type N2 45°
Alternatively:
•
Bergonzo type B5 45° SA
Complete range of nozzles:
Bergonzo type B5 45°
150 - 200 - 225 - 250 - 275 - 300 - 325 - 350 - 375 - 400 -
425 - 450 - 475 - 500 - 525 - 550 - 575 - 600.
Fluidics type N1 45°
160 - 180 - 200 - 225 - 250 - 275 - 300 - 330 - 360 - 400 -
450 - 500 - 550 - 600.
Fluidics type N2 45°
160 - 180 - 200 - 225 - 250 - 275 - 300 - 330 - 360 - 400 -
450 - 500 - 550 - 600.
Tab. M
WARNING
It is advisable to replace nozzles every year
during regular maintenance operations.
CAUTION
The use of nozzles other than those specified
by the Manufacturer and inadequate regular
maintenance may result into emission limits
non-conforming to the values set forth by the
regulations in force, and in extremely serious
cases, into potential hazards to people and ob-
jects.
The manufacturing company shall not be lia-
ble for any such damage arising from non-ob-
servance of the requirements contained in this
manual.
WARNING
Do not use any sealing products such as:
gaskets, sealing compound, or tape.
Be careful to avoid damaging the nozzle seal-
ing seat.
The nozzle must be screwed into place tightly
but not to the maximum torque value pro-
vided by the wrench.
2 mm
Fig. 21
D8833
kg/h
Pressione
mandata
bar
Pressione
ritorno
bar
kg/h
kW
RLS 310
- 410
150
21
13
51
600
21
19
106
1250
200
22
8,5
67
800
22
17,5
150
1800
300
20
7
100
1200
20
17,5
257
3000
375
20
6,5
148
1750
20
15,5
305
3600
425
20
7,5
68
1950
20
17
344
4100
RL
S 510
250
24
9
94
1120
25
15,5
210
2500
360
24
7,5
116
1380
25
14
260
3090
400
24
8,5
153
1820
25
15
355
4220
450
24
8
164
1950
25,5
16
425
5050
RLS 61
0
300
20
9,5
125
1500
20
14
250
3000
450
20
8
134
1600
20
14
380
4550
575
20
9,5
193
2300
20
17
510
6070
Summary of Contents for RLS 310/EV O2 MX
Page 2: ...Translation of the original instructions ...
Page 52: ...20182250 50 GB Appendix Electrical panel layout 0 0 0 0 0 0 0 0 ...
Page 55: ...53 20182250 GB Appendix Electrical panel layout 0 ...
Page 56: ...20182250 54 GB Appendix Electrical panel layout ...
Page 57: ...55 20182250 GB Appendix Electrical panel layout 0 0 1 2 0 0 0 1 0 ...
Page 58: ...20182250 56 GB Appendix Electrical panel layout 0 0 0 1 0 2 0 0 0 0 0 0 0 30 3 3 0 0 1 0 ...
Page 66: ......
Page 67: ......