Installation
Example RLS 100 with natural gas G20:
2nd stage operation
Gas pressure at test point 1)(Fig. 29)
= 11.2 mbar
Pressure in combustion chamber
=
2 mbar
11.2 - 2
=
9.2 mbar
A pressure of 9.2 mbar, column 1, corresponds in Tab. K on
page 26 to an output of 955 kW.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To calculate the required gas pressure at test point 1)(Fig. 29),
with the output fixed at that required for the burner in the 2nd
stage:
–
find the nearest output value in the Tab. K on page 26 for the
burner in question.
–
Read, on the right (column 1), the pressure at the test point
1)(Fig. 29).
–
Add this value to the estimated pressure in combustion
chamber.
Example RLS 100 with natural gas G20:
Desired output in 2nd stage: 955 kW
Gas pressure at an output of 210 kW
=
9.2 mbar
Pressure in combustion chamber
=
2 mbar
9.2 + 2
= 11.2 mbar
pressure required at test point 1)(Fig. 29).
+
Fig. 29
S9690