20035283
26
GB
Start-up, calibration and operation of the burner
8.10 Programming menu
GENERAL
The programming menu can be accessed using the reset push-
button only during OPERATION and in STAND-BY.
If in page menu the reset push-button is not pressed within 10
seconds the page will be automatically exited and there will be a
green led blinking for the value set.
If the number of pressures on the reset push-button exceeds the
maximum allowable, the value in memory will remain the maxi-
mum one.
If the reset push-button is pressed for more than 60 seconds, a
reset push-button error will be displayed and the control-box will
restart.
BLOCK DIAGRAM FOR ENTERING THE MENU
Tab. F
Version
Release push-button time
Led signal
page menu
N° push-button
pressing
Led visualized
(GREEN)
Exit menu
Shut Down Test
5s
t < 10s
2 Flashing
RED
/
Automatic from
flashing stops
Post Purge
10s
t < 15s
1 Flashing
GREEN
1 = 10 sec. (default)
2 = 20 sec.
3 = 30 sec.
4 = 60 sec.
5 = 120 sec.
6 = 0 sec. (disable)
1 flash
2 flash
3 flash
4 flash
5 flash
6 flash
10 sec. after
release
push-button
Light diagnosis
15s
t < 20s
2 Flashing
GREEN
1 = enable
2 = disable (default)
1 flash
2 flash
10 sec. after
release push-button
Intermittent operation
20s
t < 25s
3 Flashing
GREEN
1 = 0 disable
2 = 1 hour (default)
3 = 24 hours
1 flash
2 flash
3 flash
10 sec. after
release push-button
Last lockout memo-
rised
25s
t < 30s
4 blinks
GREEN
/
none
Display of the
type of reset
according to
table section
8.8.2
10 sec. after the
release of the but-
ton
OPERATION (WITH FLAME) AND STAND-BY
SHUT DOWN
INTERMITTENT
POST
OPERATION
2 RED
1 GREEN
2 GREEN
3 GREEN
AUTOMATIC
EXIT
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
10 SEC. AFTER
RELEASE
TEST
PURGE
LIGHT
DIAGNOSIS
20 SEC.
LAST LOCKOUT
MEMORISED
25 SEC.
4 GREEN
10 SEC. AFTER
RELEASE
S9066
5 SECS.
10 SEC.
15 SEC.
BURNER STATE
TYPE OF
FUNCTION
NUMBER OF
EXIT
BLINKS
Fig. 25