![Riello MCM 10 Technical Specifications Download Page 31](http://html1.mh-extra.com/html/riello/mcm-10/mcm-10_technical-specifications_1460115031.webp)
MULTI SENTRY
SPTMSTD2T16EREN
29
The Battery Cabinet configuration is shown below.
Other solutions may be developed on site, bearing in mind that:
-the structure of the battery enclosure must respect that described above.
-the number of batteries must remain constant (20+20 12 Volt monoblocks).
-the battery capacity (expressed in Ah) must fall within the range of 4 and 20 times the available recharging
current (see the “Technical Specifications Table”).
MODELS BATTERY BOX
AB 1320 480-T5
AB 1600 480–S5
AB 1900 480-V9
DIMENSIONS (mm)
H x L x P
400 kg
(90 empty)
730 kg
(150 empty)
1400 kg
(200 empty)
>11.5 ADDITIONAL BATTERY CHARGER
The UPS can be furnished from the factory with a more powerful battery charger mounted in place of the
standard one(on series MST 10÷40 & MSM 10÷20).
It’s possible to install the upgraded charger replacing the standard also on the site through a special installation
kit on site (on series MST 10÷20 & MSM 10÷20).
Model
10-12-15-20 kVA
30-40 kVA
Standard charger on supplied
6 Amperes
10 Amperes
Powerful charger
10 Amperes
20 Amperes
(ONLY FACTORY)