combination storage cylinders can be installed in any room where there is no specific requirement for an
electrical protection rating higher than IP X0D.
b
The room where the appliance is installed must, however, be dry to prevent the formation of rust.
b
Specified minimum distances must be respected, and the space in which the combination storage cylinder is to
be installed must be easily accessible in order to permit easy installation and assembly and subsequent inspec-
tion, maintenance and repair. In particular, access must permit the combination storage cylinder to be removed
without disassembly at the end of its useful life, and another unit to be installed in its place. Users are therefore
responsible for any costs incurred to demolish masonry or other structures preventing or impeding free access to
the space where the combination storage cylinder is to be installed.
When installing
r
KOMBI
combination storage cylin-
ders in old systems or systems requiring modernisation,
always perform the following checks:
- Make sure that the system is fitted with safety and con-
trol devices in accordance with applicable legislation
and standards.
- Make sure that the circuit has been flushed out to remo-
ve all sludge and lime scale, and has been vented and
seal tested.
- Make sure that a suitable water treatment system is
installed if the quality of the supply/recirculation water
so demands. (Refer to the reference values listed in the
table alongside).
PLACE OF INSTALLATION
INSTALLATION IN OLDER SYSTEMS AND SYSTEMS REQUIRING MODERNISATION
REFERENCE VALUES
pH
6-8
Electrical conductivity
below 200 mV/cm (25°C)
Chlorine ions
below 50 ppm
Sulphuric acid ions
below 50 ppm
Total iron
below 0,3 ppm
Alkalinity M
below 50 ppm
Total hardness
below 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
below 30 ppm