Electrical power supply
230(±10%)-50
V-Hz
Maximum power absorbed by the BAG
2
MIX
230
W
Time (opening / closing) for the mix valve
120
s
Working range of the sensor (SM)
0 ÷ +50
°C
Working temperature
0 ÷ +90
°C
Electrical protection level wall-mounted installation
IP10D
Electrical protection level “built-in” installation
IPX4D
Maximum pressure
3
bar
TECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATA
TECHNICAL DATA
DIMENSIONS AND WEIGHT
DIMENSIONS AND WEIGHT
DIMENSIONS AND WEIGHT
DIMENSIONS AND WEIGHT
DIMENSIONS AND WEIGHT
DESCRIPTION
L
440
mm
P
160
mm
H
616
mm
NET WEIGHT
16
Kg
STRUCTURE
DESCRIPTION OF THE EQUIPMENT
DESCRIPTION OF THE EQUIPMENT
DESCRIPTION OF THE EQUIPMENT
DESCRIPTION OF THE EQUIPMENT
DESCRIPTION OF THE EQUIPMENT
The BAG
2
MIX is a water separator that is only to be
used with condensing boilers (type 2006), where it
separates the water in the generator and in the plant,
when the latter is characterised by high flow rates that
exceed those developed by the generator itself. It
can also be used to manage mixed low and high tem-
perature heating systems (radiators / fan coils and
radiant panels).
It allow to manage a climatic curve for the high tem-
perature system and a second for the low temperature
system
The BAG
2
MIX unit can be built into the wall, thereby
avoiding any protrusion, or it can be wall-mounted.
The unit comes complete with the wiring necessary
for connecting it to the boiler for typical BAG
2
MIX in-
stallations, near to the boiler itself (cable length 2 m).
GENERAL
1
Automatic high limit thermostat low temperature
system
2
Low temperature system NTC sensor
3
Low temperature system pump
4
High temperature system pump
5
Mixing bottle
6
Air vent valve
7
Low temperature system thermometer
8
High temperature system thermometer
9
Mixing valve
10 Electrical connection board