PARAMETER DESCRIPTION

004

To alter the measurement unit: 0 = METRIC measurement units / 1 = IMPERIAL measurement units.  The fi gures are expressed in decimal format (one fi gure) for values 

between -9°C and +99°C, and in whole number format for values ≤ -10°C and ≥ 100°C. The visualisation in °F (Fahrenheit) is always expressed in whole number format. 

006

To enable/disable the acoustic signal, 0 = buzzer OFF / 1 = buzzer ON

301

To set the type of hydraulic confi guration for the boiler: 0 = HEATING ONLY - 1 = INSTANTANEOUS FLOW SWITCH - 2 = INSTANTANEOUS FLOW METER - 

3 = STORAGE TANK WITH PROBE - 4 = STORAGE TANK WITH THERMOSTAT

Factory value = 2 (do not alter). If the electronic board is replaced, make sure this parameter is set at 2

302

To set the type of water pressure transducer: 0 = water pressure switch - 1 = pressure transducer

Factory value = 1 (do not alter). If the electronic board is replaced, make sure this parameter is set at 1.

303

To enable the “semi-automatic fi lling” function when a pressure transducer and fi lling solenoid valve are installed in the boiler.

Factory value = 0 (do not alter). If the electronic board is replaced, make sure this parameter is set at 0.

304

Only appears if 303 = 1  NOT AVAILABLE ON THIS MODEL.

305

To disable the vent cycle function. Factory value = 1. Set the parameter at 0 to disable the function.

306

To alter the minimum number of fan rotations.

307

To alter the maximum number of fan rotations.

308

To regulate slow ignition (it can be programmed within the range 306 - 307).

309

To alter the maximum fan rpm in heating mode (it can be programmed within the range 306 - 307).

310

To modify the heat output in heating mode. Factory value = 

309, but it can be programmed within the range 306 - 309.

For more details about the use of this parameter, refer to paragraph “4.12 Range rated”.

311

To confi gure the operation of a supplementary relay (only if board BE09 (accessory kit) is installed) in order to bring a phase (230V AC) to a second heating pump 

(supplementary pump) or to a zone valve. Factory value =

 0, but it can be programmed within the range 0 - 2 with the following meaning: 

311= 0 - 

control depends on the confi guration of the wiring of the BE09 board (jumper cut: supplementary pump - jumper present: zone valve)

311= 1 - control of the zone valve

311= 2 - control of the supplementary pump

312

Used to reset the operating hours counter in certain conditions (for more details, see “4.13 Faults and reporting”, fault 

A91).

Factory value = 0. Bring the value to 1 to reset the fl ue gas probe hour counter after the cleaning of the primary heat exchanger.

When the reset procedure has been completed, the parameter will return automatically to 0.

313

This parameter allows the regulation of slow ignition in burner re-ignitions following shutdowns due to the set point temperature being reached.

Adjustment is possible between the minimum fan speed value (306) and the speed value during slow ignition (308)

401

For high temperature systems, this parameter allows the setting of the hysteresis value used by the adjustment board to calculate the delivery temperature for burner switch-off:

SWITCH-OFF TEMPERATURE = HEATING SE 401. 

Factory value =

 5°C, but it can be set within the range 2 - 10°C.

402

For high temperature systems, this parameter allows the setting of the hysteresis value used by the adjustment board to calculate the delivery temperature for burner 

ignition: IGNITION TEMPERATURE = HEATING SETPOINT - 402.

 Factory value = 5°C, but it can be set within the range 2 - 10°C.

403

For low temperature systems, this parameter allows the setting of the hysteresis value used by the adjustment board to calculate the delivery temperature for burner 

switch-off: SWITCH-OFF TEMPERATURE = HEATING SE 403.

Factory value = 3°C, but it can be set within the range 2 - 10°C.

404

For low temperature systems, this parameter allows the setting of the hysteresis value used by the adjustment board to calculate the delivery temperature for burner 

ignition: IGNITION TEMPERATURE = HEATING SETPOINT - 404.

Factory value = 3°C, but it can be set within the range 2 - 10°C.

405

Pump with variable proportional speed. NOT AVAILABLE ON THIS MODEL.

408

Used to set the boiler for cascade applications via an OT+ signal. Not applicable with this boiler model.

409

Used to activate the screed heater function (for more details, refer to paragraph “4.7 Screed heater function”).

Factory value = 0, with the boiler OFF.  Set the value at 1 to activate the screed heater function on the low temperature heating areas.

The param

eter returns automatically to 0 when the screed heater function ends, but the function can also be interrupted by manually setting the value at 0.

410

Used to modify the forced heating off timer with regards the delay time for re-igniting the burner if it is OFF because the heating temperature has been reached. Factory 

value = 3 minutes, but it can be se t at a value between 0 and 20 min.

411

Used to annul the HEAT TIME RESET function and REDUCED MAX. HEATING OUTPUT TIMER, during which the fan speed is limited to a range between the minimum 

and 60% of the max. heating output set, with a 10% increase every 15 minutes. Factory value = 0. Set at 1 to reset the timer.

415

Used to specify the type of area to be heated. Choose from the following options: 

0 = HIGH TEMPERATURE (factory setting)

1 = LOW TEMPERATURE

416

Used to specify the maximum heating setpoint value that can be set:

range 20°C - 80.5°C, default 80.5°C for high temperature systems 

range 20°C - 45°C, default 45°C for low temperature systems

Note: the value of 

416 cannot be lower than 417.

417

This parameter is used to specify the minimum heating setpoint value that can be set:

range 20°C - 80.5°C, default 40°C for high temperature systems

range 20°C - 45°C, default 20°C for low temperature systems

Note: the value of 

417 cannot be higher than 416.

418

Used to activate temperature control when the system is connected to an outdoor temperature sensor.

Factory value = 0 (the boiler always works with a fi xed point). If the parameter is set at 1 and an outdoor temperature sensor is connected, the boiler works in temperature 

control mode. If the outdoor temperature sensor is disconnected, the boiler always works with a fi xed point.

See paragraph “4.4 Setting the thermoregulation” for more details about this function.

419

Used to set the number of the compensation bend used by the boiler in temperature control mode. Factory value = 2.0 for high temperature systems, and 0.5 for low 

temperature systems. The parameter can be programmed within the range 1.0 - 3.0 for high temperature systems, or 0.2 - 0.8 for low temperature systems. See para-

graph “4.4 Setting the thermoregulation” for more details about this function.

5.2 

Parameters description

Some of the following functions may not be available depending on the machine type and access level

.

SERVICE PARAMETERS

Value

        min                                            max

Password 

level

Value set in

the factory

Personalised 

values

DHW

510

DHW DELAY

0 sec

60 sec

SERVICE

0 sec

512

DHW POST-CIRC. ON HEATING RETURN

0

1

SERVICE

0

513

RETURN POST-CIRC TIME

1

255

SERVICE

6

TECHNICAL

701

ALARM HISTORY ACTIVATION

0

1

SERVICE

0 (the value 

automatically 

changes to 1 after 2 

hours of operation)

706

SERVICE CALL FUNCTION

0

2

SERVICE

2

707

SERVICE DEADLINE

0

255

SERVICE

52

708

HIGH EFFICIENCY MODE

1

SERVICE

0

CONNECTIVITY

 

801

BUS 485 CONFIG.

0  

2

SERVICE

0

803

OT+ CONFIG.

1

SERVICE

1

*301:

  0 = HEATING ONLY - 1 = INSTANTANEOUS FLOW SWITCH - 2 = INSTANTANEOUS FLOW METER - 3 = STORAGE TANK WITH PROBE

 

4 = STORAGE TANK WITH THERMOSTAT

Summary of Contents for 20197878

Page 1: ...START KIS EN INSTALLER AND USER MANUAL RO MANUAL DE INSTALARE SI UTILIZARE HU TELEP T I FELHASZN L I K ZIK NYV EL PT MANUAL DO INSTALADOR E UTILIZADOR BG C 5 0 8...

Page 2: ...rences Aceast central termic poate fi adaptat la cerin ele de c ldur ale sistemului i de fapt este posibil s se seteze parametrul cu valoarea nominal a a cum se arat n paragraful respectiv Dup setarea...

Page 3: ...t for the pressure to increase check on the boiler di splay that the value reaches 1 1 5 bar then close the filling tap section 8 General boiler layout 1 If the boiler is not used for a long period of...

Page 4: ...l 8 8 Expansion tank pre loading heating bar 1 1 DHW operation Maximum pressure bar 8 8 Minimum pressure bar 0 5 0 5 Quantity of hot water with t 25 C l min 14 3 17 2 with t 30 C l min 11 9 14 3 with...

Page 5: ...ices and solar devices DEVICES CLASS BONUS OUTDOOR TEMPERATURE SENSOR II 2 OT CONTROL PANEL V 3 OUTDOOR TEMPERATURE SENSOR OT CONTROL PANEL VI 4 Parameter Symbol 25 KIS 30 KIS Unit Seasonal space heat...

Page 6: ...itch itself on any lockout condition for ex due to a lack of gas or electrical supply or the intervention of a safety device therefore deactivates the protection If the machine is left without power f...

Page 7: ...y It is forbidden to use gas and or water pipes to earth electrical appliances Use the power cable supplied to connect the boiler to the mains power supply If the power cable has to be replaced use a...

Page 8: ...80 465 7 700 9 100 25 62 310 500 Maximum length that can be installed ONLY with class H1 discharge pipes compact twin flue pipe Fan rotationsrpm Pipes 50 Pipes 60 Pipes 80 P at boiler outlet CH DHW Ma...

Page 9: ...access the INFO menu 5 3 INFO menu item I018 to check that the pressure value reaches 1 1 5 bar close the filling tap A 15bar NOTE if the mains pressure is less than 1 bar keep the filling tap A open...

Page 10: ...Setting the thermoregulation The thermoregulation is only available if an external probe is connected and is only active for the HEATING function THERMOREGULATION is enabled in the following way set p...

Page 11: ...function is activated the DHW thermostats for burner ON OFF switch from the relative value to the absolute one ANTI OSCILLATION function 4 If this function is activated the boiler self configures to A...

Page 12: ...and 2 minus the difference found Example CO2 value measured with the casing closed 8 5 CO2 value measured with the casing open 8 3 value to be set for CO2 with the casing open 8 8 value to be set for...

Page 13: ...a temperature of around 50 C The intervention of the Technical Assistance Centre is required Fault A91 The boiler has a self diagnosis system that signals the need to clean the primary heat exchanger...

Page 14: ...so available in a kit Vacuum away any residue produced by the cleaning Rinse with water being careful NOT to damage the retarder insulation panel b In case of stubborn deposits of combustion products...

Page 15: ...ICABLE ON THIS MODEL 409 SCREED HEATER 0 1 INSTALLER if boiler in OFF and LT systems 0 410 HEATING OFF 0 min 20 min INSTALLER 3 min 411 RESET HEATING TIMES 0 1 INSTALLER 0 415 MAIN LT ZONE 0 1 INSTALL...

Page 16: ...ner switch off SWITCH OFF TEMPERATURE HEATING SETPOINT 403 Factory value 3 C but it can be set within the range 2 10 C 404 For low temperature systems this parameter allows the setting of the hysteres...

Page 17: ...ay in seconds is imposed on pump and fan activation when there is a DHW request 511 Enabling of special DHW functions 0 no function 1 ow switch ow meter start up delay 2 with OFF due to overtemperatur...

Page 18: ...CH delivery temperature DHW temperature WINTER MODE The boiler activates the heating and DHW function The presence of the icon indicates a heat request and burner switch on SUMMER MODE The boiler acti...

Page 19: ...er is not used for a long time the following operations must be carried out set the OFF status set the system s main switch to off turn off the fuel and water taps of the heating and domestic hot wate...

Page 20: ...binetul de umplere sec iunea 8 consulta i Structura cazanului 1 a tepta i p n ce presiunea cre te verifica i pe ecranul centralei ca valoarea s ajung la 1 1 5 bar apoi nchide i robinetul de umplere se...

Page 21: ...1 000 Vas de expansiune cu membran l 8 8 Pre nc rcare vas de expansiune nc lzire bari 1 1 Func ionare pentru circuitul de ap menajer Presiune maxim bari 8 8 Presiune minim bari 0 5 0 5 Cantitate de a...

Page 22: ...ru dispozi tivele de control al temperaturii i dispozitivele solare COMPONENT CLAS BONUS SOND EXTERN II 2 COMAND DE LA DISTAN OT V 3 SOND EXTERN COMAND DE LA DISTAN OT VI 4 2 1 Date Erp Parametru Simb...

Page 23: ...b Pentru a beneficia de aceast protec ie bazat pe func ionarea arz torului centrala trebuie s poat fi pornit prin urmare orice condi ie de blocare de exemplu lipsa aliment rii cu gaz sau cu energie e...

Page 24: ...or de gaz i sau de ap ca mp m ntare pentru aparaturile electrice Pentru conexiunea electric folosi i cablul de alimen tare din dotare n cazul nlocuirii cablului de alimentare utiliza i un cablu de tip...

Page 25: ...365 500 30 KIS 6 900 8 300 4 16 80 180 7 100 8 500 8 26 130 260 7 200 8 500 11 32 160 300 7 300 8 700 14 38 190 342 7 400 8 800 17 44 220 383 7 500 8 900 19 50 250 431 7 600 9 000 22 56 280 465 7 700...

Page 26: ...i meniul INFO 5 3 Meniul INFO elementul I018 pentru a verifica dac valoarea presiunii ajunge la 1 1 5 bar nchide i robinetul de umplere A 15bar NOT dac presiunea re elei este sub 1 bar men ine i desch...

Page 27: ...eaz temporar aceast func ie n timpul execu iei pictograma de presiune a apei clipe te i afi ajul arat A C 02 5 4 3 Ciclul de evacuare a aerului Aduce i ntrerup torul general al instala iei pe pozi ia...

Page 28: ...la minim MIN i nu este oprit n caz de oprire a arz torului din cauza supratemperaturii n modul ap menajer cu cerere prezent Func ia TERMOSTATE ABSOLUTE 3 La activarea acestei func ii termostatele de a...

Page 29: ...nt de diferen a de valoare observat ntre carcasa nchis i carcasa deschis dac este necesar regla i CO2 la valoarea indicat n tabel 1 i 2 minus diferen a observat Exemplu valoare CO2 m surat cu carcasa...

Page 30: ...cea a valorii presiunii apei din sistem 2 sec Anomalie A60 centrala func ioneaz normal dar nu asigur stabilitatea temperaturii apei menajere care oricum este furnizat la o temperatur de aproape 50 C...

Page 31: ...II METALICE CARE POT DETERIORA COMPONENTELE Cur a i spa iile dintre spire utiliz nd o lam cu grosimea de 0 4 mm eventual disponibil n kit Aspira i eventualele resturi produse de cur are Cl ti icuap av...

Page 32: ...min 20 min INSTALATOR 3 min 411 RESETARE TIMPI NC LZ 0 1 INSTALATOR 0 415 ZON P TS 0 1 INSTALATOR 0 416 TEMP MAX ZONA P TEMP MIN ZONA P TR 80 5 TS 45 0 INSTALATOR TR 80 5 TS 45 0 417 TEMP MIN ZONA P...

Page 33: ...aloarea din fabric pentru acest parametru este 3 C i poate modi cat n intervalul 2 10 C 404 Pentru instala ii la temperatur sc zut acest parametru permite setarea valorii de histerezis utilizate de pl...

Page 34: ...supratemperaturii pentru ap menajer cu preluare n curs ventilatorul este men inut la viteza de pornire pentru a reduce timpii de a teptare la repornire 3 termostate absolute ap menajer 4 func ie ap me...

Page 35: ...erior interfa a trece la afi area st rii active n acel moment b Regla i termostatul de mediu la temperatura dorit 20 C sau dac instala ia este dotat cu un cronotermostat sau programator orar verifica...

Page 36: ...Oprirea pentru perioade lungi de timp Neutilizarea centralei pentru o perioad ndelungat de timp presupune exe cutarea urm toarelor opera iuni seta i la starea OPRIT pozi iona i ntrerup torul general...

Page 37: ...csap kinyit s val 8 szakasz l sd Kaz n elrendez se 1 v rja meg a nyom s n veked s t ellen rizze a kaz n kijelz j n hogy az rt k el ri e az 1 1 5 bar rt ket majd csukja be a t lt csapot 8 szakasz l sd...

Page 38: ...sz m ra rendelkez sre ll max eme l nyom s mbar 408 408 a k vetkez hozamn l l h 1 000 1 000 Membr nos t gul si tart ly l 8 8 T gul si tart ly el t lt se f t s bar 1 1 HMV zemm d Max nyom s bar 8 8 Min...

Page 39: ...ALKATR SZ OSZT LY B NUSZ K LS SZONDA II 2 OT T VVEZ RL V 3 K LS SZONDA OT T VVEZ RL VI 4 Param ter Jel 25 KIS 30 KIS Me Szezon lis helyis gf t si energiahat konys gi oszt ly A A V zmeleg t si energiah...

Page 40: ...iztos tja a kaz n v delm t eg szen 0 C leveg h m rs kletig a be p t s hely n b Ez a v delem az g zemel s n alapul gy a kaz nnak k pesnek kell lennie a begyullad sra vagyis minden olyan helyzetben amik...

Page 41: ...lla mind f zis f zis ramell t ssal k pes ze melni Tilos a g zcs vet vagy a v zcs vet haszn lni elektromos f lde l s c lj ra Az elektromos csatlakoz s c lj ra haszn lja azt a k belt amely a k sz l khez...

Page 42: ...383 7 500 9 200 27 61 305 431 7 600 9 300 29 67 335 465 7 700 9 400 32 73 365 500 30 KIS 6 900 8 300 4 16 80 180 7 100 8 500 8 26 130 260 7 200 8 500 11 32 160 300 7 300 8 700 14 38 190 342 7 400 8 80...

Page 43: ...men be 5 3 INFO men sor I018 hogy ellen rizze hogy a nyom s rt k el ri e az 1 1 5 bar rt ket z rja le a t lt csapot A 15bar Megjegyz s ha a h l zati nyom s kisebb mint 1 bar tartsa nyitva a t lt csa p...

Page 44: ...meg lehet szak tani ha a kaz n nincs OFF llapotban egy haszn lati meleg v z ig nnyel 4 4 H szab lyoz s be ll t sa A h szab lyoz s csak csatlakoztatott k ls szond val rhet el s csak a F T S funkci n l...

Page 45: ...ci nak az aktiv l s val az g BE KI HMV termoszt tjai tjut nak a relat v rt kr l az abszol t rt kre ING Z SG TL funkci 4 Ezzel a funkci val a kaz n nmag t konfigur lja az ABSZOL T TERMOSZ T TOKON ha az...

Page 46: ...l m rt CO2 rt k 8 3 nyitott burkolattal CO2 erre az rt kre ll tand be 8 8 z rt burkolattal a CO2 rt ke 9 0 a CO2 rt k be ll t s hoz forgassa az ramutat j r s val megegyez ir nyba a maxim lis teljes t...

Page 47: ...rs kleten biztos t A m szaki gyf lszolg lat beavatkoz s ra van sz ks g Rendelleness g eset n A91 a kaz n el van l tva egy nellen rz rend szerrel amely adott k r lm nyek k zti zemel s ssz r inak sz m n...

Page 48: ...zel gyelve arra hogy ne s rtse meg a retarder szigetel panelj t b Ha az g sterm kek makacsan lerak dnak a h cser l fel let n tiszt tsa meg term szetes feh r ecet permetez s vel gyelve arra hogy ne s r...

Page 49: ...ELEP T csak ha 418 1 MH 2 0 AH 0 4 420 P Z NA JSZAKAI KOMP 0 1 0 432 P LETT PUS 5 perc 20 perc 5 perc 433 K LS SZONDA REAKTIVIT S 0 255 20 HMV 0 508 HMV MIN H M 37 5 C 49 0 C TELEP T 37 5 C 509 HMV MA...

Page 50: ...a kaz n kaszk d alkalmaz sokhoz t rt n be ll t s t az OT jel seg ts g vel Nem alkalmazhat enn l a kaz nmodelln l 409 Lehet v teszi az esztrichmeleg t funkci aktiv l s t tov bbi r szletek rt l sd az 4...

Page 51: ...se A CFS jel megjelen t se ta eltelt napok sz ma 707 0 706 Ez a param ter lehet v teszi a kaz n id szakos vez rl s t a 707 param terben be ll tott m k d si id szaknak megfelel en H rom be ll t si rt...

Page 52: ...k nt 7 3 F t si alap rt k be ll t sa k ls szond val Csatlakoztatott k ls szond val opcion lis s beiktatott h szab lyoz ssal param ter 418 1 az el remen h m rs klet rt k t a rendszer automa tikusan be...

Page 53: ...b id szakra Amennyiben a kaz nt hosszabb ideig nem k v nja haszn lni az al bbi m veleteket v gezz k el ll tsa OFF llapotba ll tsa a k sz l k f kapcsol j t kikapcsolt ll sba z rja el a f t s HMV rendsz...

Page 54: ...54 b b b 8 b b b b b b b b b 1 bar 8 1 1 1 5 bar 8 1 OFF off b 60 30 C 30 a a a OFF a a a a a a a a b a b a 1...

Page 55: ...42 42 II2H3P GR II2HY203P GR II2H3P GR II2HY203P GR V Hz 230 50 230 50 IP X5D X5D W 30 32 0 09 2 80 0 08 2 26 bar 3 3 bar 0 25 0 45 0 25 0 45 C 90 90 H2O C 20 80 20 45 20 80 20 45 mbar 408 408 l h 1...

Page 56: ...39 5 500 5 500 5 500 5 500 7 000 6 900 6 900 6 800 8 700 8 300 8 500 7 900 1 500 1 500 2 050 1 700 C 10 80 125 80 80 9 200 7 000 C 10 80 125 80 80 2 100 2 100 811 2013 BONUS II 2 OT V 3 OT VI 4 25 KIS...

Page 57: ...g kg 0 5 Cu mg kg 0 1 6 bar b b 3 2 UNI 7129 7131 CEI 64 8 b C 1 B23P B53P 2 C 10 C13 C13x C33 C33x C43 C43x C53 C53x C63 C63x C83 C83x C93 C93x A B 0 C 60 C START 25 KIS C A B C 5 C 0 C b 0 C 0 C 15...

Page 58: ...OFF WINTER SUMMER OT setpoint OT A B setpoint I005 INFO setpoint OT I017 INFO setpoint TA OT 311 1 info I016 OT 803 0 SERVICE 3 INFO 3 5 mm EN 60335 1 3 230 Volt 50 Hz EN 60335 1 b b L N b b HAR H05V2...

Page 59: ...100 8 500 8 26 130 260 7 200 8 500 11 32 160 300 7 300 8 700 14 38 190 342 7 400 8 800 17 44 220 383 7 500 8 900 19 50 250 431 7 600 9 000 22 56 280 465 7 700 9 100 25 62 310 500 H1 rpm 50 60 80 P m...

Page 60: ...80 4 5 4 5 0 5 m 80 125 4 5 0 5 m b b b 3 b b b b 10 b 25 Pa n 1 1 b 200 Pa b 3 8 C 10 rpm 3 10 A C A A40 A41 A42 A INFO 5 3 INFO I018 1 1 5 bar A 15bar 1 bar A OFF A 1 1 5 bar 1 1 5 bar 3 11 OFF C C...

Page 61: ...C 5 C 10 5 0 5 10 15 20 420 420 420 1 20 C 16 C 90 80 70 60 50 40 30 20 10 C C 20 15 10 5 0 5 10 15 20 setpoint 20 C 16 C 5 5 crono OT 7 2 setpoint 4 5 1 2 3 2 PHO PH 1 PH2 PH3 PH1 PH3 PHO 60 60 55 C...

Page 62: ...damassetto setpoint 20 C 1 0 20 C 6 22 C 12 24 C 18 26 C 2 0 28 C 12 30 C 3 0 32 C 4 0 35 C 5 0 35 C 6 0 30 C 7 0 25 C 168 7 OFF 409 1 R c S OFF 409 0 INFO I001 4 8 b CO2 0 2 1 4 2 3 MAX MIN Co 2 0 0...

Page 63: ...S 1 500 2 050 30 KIS 1 500 1 700 5 G20 G31 25 KIS 30 KIS 5 500 5 500 CO2 4 8 CO2 3 7 CO2 CO2 1 2 CO2 8 5 CO2 8 3 CO2 8 8 CO2 9 0 CO2 CO2 CO2 CO2 1 2 CO2 CO2 4 11 G20 LPG LPG G20 3 7 B B 4 9 4 10 b b b...

Page 64: ...INFO 5 3 INFO I018 1 1 5 bar A A A40 A41 9 INFO 5 3 INFO I035 5sec 2 A60 50 C A91 A91 A91 2500 INFO I015 100 2 500h 25 312 1 4 14 301 302 SERVICE 306 307 308 309 310 708 b 708 0 A10 A11 A20 A30 A40 A...

Page 65: ...65 EL 5 1 3 bar b b b 4 8 b b b 3 7 A B 4 C b 0 4 mm b b 6 Nm 1 2 3 4 3 7 A B 4 C b 6 Nm A A B C D A B C b b b 4 2 b...

Page 66: ...BT 45 0 AT 80 5 BT 45 0 417 P 20 P AT 40 BT 20 418 P 0 1 0 419 P AT 1 0 BT 0 2 AT 3 0 BT 0 8 418 1 AT 2 0 BT 0 4 420 P 0 1 0 432 5 min 20 min 5 min 433 0 255 20 0 508 37 5 C 49 0 C 37 5 C 509 49 0 C 6...

Page 67: ...OINT 402 5 C 2 10 C 403 SETPOINT 403 3 C 2 10 C 404 SETPOINT 404 3 C 2 10 C 405 408 OT 409 4 7 0 OFF 1 0 0 410 3 0 20 411 60 10 15 0 1 415 0 1 416 setpoint 20 C 80 5 C 80 5 C 20 C 45 C 45 C 416 417 41...

Page 68: ...I034 Id I035 Rev fw I038 wi wi I039 1 I040 2 I041 3 I042 4 I043 5 I044 CFS CFS 707 0 419 2 0 0 5 1 0 3 0 0 2 0 8 4 4 420 0 1 4 4 432 433 501 507 508 setpoint 509 setpoint 510 511 2 5 511 0 1 2 OFF 3...

Page 69: ...F OFF C 50 4 C 50 8 15bar C 50 8 C 50 4 7 2 setpoint setpoint 0 5 C C 0 0 6 C 0 5 6 5 setpoint 7 3 setpoint 418 1 setpoint C 5 C 5 setpoint 5 5 C 418 0 Buzzer 006 Buzzer 1 0 100 6 500 rpm 65 0 A B set...

Page 70: ...C 35 C AF1 5 C 55 C AF2 24 30 7 7 OFF 7 8 Lc o 2 C 5 0 8 2 7 9 701 1 SERVICE INFO I039 I043 5 OT 7 5 10 A 2 Res 7 10 Gateway Riello Wifi key wifi Riello Wifi key gateway 801 SERVICE wifi C 5 7 2 C 5...

Page 71: ...ces s rio restaurar a press o abrindo a v lvula de enchimento se o 8 ver Layout da caldeira 1 aguardar que a press o aumente verificar no ecr da caldeira que o valor atinge 1 1 5 bar depois fechar a v...

Page 72: ...1 000 1 000 Vaso de expans o de membrana l 8 8 Pr carga vaso de expans o aquecimento bar 1 1 Exerc cio sanit rio Press o m xima bar 8 8 Press o m nima bar 0 5 0 5 Quantidade de gua quente com t 25 C l...

Page 73: ...ecimento ambiente dispositivos de controlo de temperatura e dispositivos solares COMPONENTE CLASSE B NUS SONDA EXTERNA II 2 CONTROLO REMOTO OT V 3 SONDA EXTERNA CONTROLO REMOTO OT VI 4 Par metro S mbo...

Page 74: ...ada no funcionamento do queima dor a caldeira deve estar em condi o de ser ligada isso implica que qualquer condi o de bloqueio p ex falta de g s ou alimenta o el c trica ou ainda interven o de uma se...

Page 75: ...m alimenta o fase neutro ou fase fase proi bido o uso de tubos de g s e ou gua como tomada de terra de aparelhos el ctricos Para a liga o el trica utilizar o cabo de alimenta o em dota o No caso de su...

Page 76: ...7 300 9 000 19 46 230 342 7 400 9 100 23 53 265 383 7 500 9 200 27 61 305 431 7 600 9 300 29 67 335 465 7 700 9 400 32 73 365 500 30 KIS 6 900 8 300 4 16 80 180 7 100 8 500 8 26 130 260 7 200 8 500 11...

Page 77: ...in tes opera es abrir a torneira de enchimento A rodando a no sentido anti hor rio aceder ao menu INFO 5 3 Menu INFO linha I018 para verificar se o valor da press o atinge 1 1 5 bar fechar a torneira...

Page 78: ...entila o tamb m pode ser interrompido se a caldeira n o estiver no estado OFF por um pedido de calor de AQS 4 4 Configura o da termorregula o A termorregula o s est dispon vel com uma sonda externa li...

Page 79: ...gura se em TERM STATOS ABSOLUTOS em caso de queimador desligado devido a sobretemperatura em AQS com retira da em curso quando o queimador desligado o ventilador mantido no m nimo Os term statos volta...

Page 80: ...o 8 3 valor com o qual regular CO2 com revestimento aberto 8 8 valor com o qual encontrar CO2 com revestimento fechado 9 0 para as regula es do valor de CO2 rodar o parafuso de regula o da pot ncia m...

Page 81: ...ma de autodiagn stico que pode com base nas horas totalizadas em condi es particulares de funcionamento sinalizar a necessidade de interven o para a limpeza do permutador prim rio c digo de alarme A91...

Page 82: ...impeza Lavar com gua tendo o cuidado de N O danificar o painel isolante do retardador b No caso de dep sitos persistentes de produtos de combust o na superf cie do permutador limpar atrav s da pulveri...

Page 83: ...OR DE CONTRAPISO 0 1 INSTALADOR se caldeira em OFF e instala es BT 0 410 DESLIGADO AQUECIMENTO 0 min 20 min INSTALADOR 3 min 411 REINICIA TEMPO DE AQUEC 0 1 INSTALADOR 0 415 ZONA P BT 0 1 INSTALADOR 0...

Page 84: ...5 C pode ser alterado no intervalo 2 C 10 C 403 Para instala es de baixa temperatura este par metro permite de nir o valor de histerese utilizado pela placa de regula o para calcular a temperatura de...

Page 85: ...it rio 509 Para con gurar o setpoint m ximo sanit rio 510 S vis vel quando o par metro 511 2 ou 5 introduzido um atraso em segundos na ativa o da bomba e do ventilador quando h um pedido de calor de A...

Page 86: ...esse momento b Regular o term stato ambiente temperatura desejada 20 C ou se a instala o estiver equipada com um cronoterm stato ou programador hor rio verificar se est ativo e regulado 20 C Depois co...

Page 87: ...per odos A n o utiliza o da caldeira durante um longo tempo envolve a execu o das seguintes opera es configurar o estado OFF posicionar o interruptor geral da instala o em desligado fechar as torneir...

Page 88: ...88 b b b b b b b b RIELLO b b b b 1 bar 8 1 1 1 5 bar 8 1 b 60 30 C 30 a a a a a a a a a a a b a b a 1...

Page 89: ...203P BG II2H3P BG II2HY203P BG V Hz 230 50 230 50 IP X5D X5D W 30 32 0 09 2 80 0 08 2 26 bar 3 3 bar 0 25 0 45 0 25 0 45 C 90 90 C 20 80 20 45 20 80 20 45 mbar 408 408 l h 1 000 1 000 l 8 8 bar 1 1 ba...

Page 90: ...39 0 39 Sm h 0 33 0 42 kg h 0 39 0 39 rpm 5 500 5 500 5 500 5 500 rpm 7 000 6 900 6 900 6 800 rpm 8 700 8 300 8 500 7 900 rpm 1 500 1 500 2 050 1 700 C 10 80 125 80 80 rpm 9 200 7 000 C 10 80 125 80 8...

Page 91: ...kg 0 5 Cu mg kg 0 1 6 bar b b 3 2 b 1 B23P B53P forced open 2 C 10 C13 C13x C33 C33x C43 C43x C53 C53x C63 C63x C83 C83x C93 C93x A B 0 C 60 C START 25 KIS C A B C ANTI FREEZE 5 C 0 C b 0 C 15 C b 8...

Page 92: ...5 OT 803 1 SERVICE OFF WINTER SUMMER OT OT A B DOMESTIC HOT WATER COMFORT I005 INFO OT I017 INFO TA OT 311 1 INFO I016 OT 803 0 SERVICE 3 INFO SETTINGS 230 V 50 Hz EN 60335 1 b b L N b b HAR H05V2V2 F...

Page 93: ...7 100 8 500 8 26 130 260 7 200 8 500 11 32 160 300 7 300 8 700 14 38 190 342 7 400 8 800 17 44 220 383 7 500 8 900 19 50 250 431 7 600 9 000 22 56 280 465 7 700 9 100 25 62 310 500 H1 50 60 80 P m 25...

Page 94: ...b b C 10 kg h b b 80 80 4 5 4 5 0 5 m 80 125 4 5 0 5 m b b b 3 b b b b 10 b 25 Pa 1 1 b 200 Pa b 3 8 C 10 3 10 A C A A40 A41 A42 A INFO I018 1 1 5 bar A 15bar 1 bar A A 1 1 5 bar 1 1 5 bar 3 11 C C 3...

Page 95: ...T AT 1 0 0 8 0 6 0 4 0 2 T BT 20 C 5 5 0 20 C 7 3 90 80 70 60 50 40 30 20 10 30 25 20 15 5 C 20 C 5 C 10 5 0 5 10 15 20 C C 420 420 420 1 20 C 16 C 90 80 70 60 50 40 30 20 10 20 15 10 5 0 5 10 15 20...

Page 96: ...viene mantenuto al minimo MIN per ridurre i tempi di attesa alla ripartenza 3 Termostati sanitari assoluti 4 Funzione sanitario smart antipendolazione 5 Tutte le quattro precedenti funzioni attive DH...

Page 97: ...008 INFO 5 C 0 5 6 rpm b CO 15 95 C 75 C b 3 3 65 C 4 9 LPG 306 307 308 309 313 3 G20 LPG G31 25 KIS 7 000 8 700 6 900 8 500 rpm 30 KIS 6 900 8 300 6 800 7 900 rpm 4 G20 LPG G31 25 KIS 1 500 2 050 rpm...

Page 98: ...0 8000 8500 9000 9500 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 25 KIS 30 KIS rpm kW 4 13 Axx A10 2 10 A Res 5 b A41 0 3 bar A41 10 A40 4 A 1 4 A 0 A40 A INFO I018 1 1 5 bar A A A40 A41 9 INFO I03...

Page 99: ...nel sifone altrimenti provvedere al riempimento b b b 4 8 b b b 3 7 A B 4 C 0 4 mm Aspirare gli eventuali residui prodotti dalla pulizia b 4 6 Nm 1 2 3 4 3 7 A B 4 C 4 6 Nm A10 A11 A20 A30 A40 A41 A4...

Page 100: ...HEATER 0 1 INSTALLER 0 410 HEATING OFF 0 min 20 min INSTALLER 3 min 411 RESET HEATING TIMES 0 1 INSTALLER 0 415 MAIN LT ZONE 0 1 INSTALLER 0 416 MAX TEMP MAIN ZONE MIN TEMP MAIN ZONE HT 80 5 LT 45 0 I...

Page 101: ...CE min max CONFIGURATION 302 PRESSURE TRANSD TYPE 0 1 SERVICE 1 303 ENABLE FILLING 0 1 SERVICE 0 304 PRESSUREATSTARTOFFILLING 305 VENTING CYCLE 0 1 SERVICE 1 HEATING 401 HIGH TEMP HYSTERESIS OFF 2 10...

Page 102: ...40 2 I041 3 I042 4 I043 5 I044 CFS CFS 707 0 419 2 0 0 5 1 0 3 0 0 2 0 8 4 4 420 0 1 4 4 432 433 501 507 508 509 510 511 2 5 511 0 1 2 3 4 5 512 513 701 0 1 2 706 707 0 1 707 4 CFS 707 0 SFS STOP FOR...

Page 103: ...INFO 1 3 2 3 CO WIFI C F rpm bar psi 7 1 3 psi bar rpm F C 1 88 8 4 4 3 b 20 C 7 1 1 C 50 4 C 50 8 15bar C 50 8 C 50 4 7 2 0 5 C C 0 0 6 C 0 5 6 5 7 3 418 1 C 5 C 5 5 5 C 418 0 006 Buzzer 1 0 100 6500...

Page 104: ...C 35 C AF1 5 C 55 C AF2 30 24 7 7 OFF 7 8 Lc o 2 C 5 0 8 2 7 9 701 1 SERVICE INFO I039 I043 5 OT 7 5 2 10 A Res 7 10 GATEWAY Riello WiFi key Riello WiFi key 801 SERVICE wifi C 5 7 2 C 5 7 2 I038 RADIO...

Page 105: ...l ctrodo 12 Burner Arz tor g Queimador 13 Flue gas air intake cap Capacul de admisie a aerului pentru F stg z leveg csatlakoz kupak Tampa de entrada de ar de fumo 14 Flue gas exhaust Evacuare gaze de...

Page 106: ...ndszer r t csap szifon lefoly EL PT v lvula de seguran a torneira de descarga da instala o dreno de sif o BG C 5 0 8 C D A B C 2 x 12mm 12mm 12mm EN Weight RO Greutate HU S ly EL PT Peso BG 25 KIS 28...

Page 107: ...ran a 3 Hidraulikus h romutas szelep V lvula hidr ulica de tr s vias 4 Nyom s talak t Transdutor de press o 5 Automatikus by pass By pass By pass autom tico 6 HMV szonda Sonda de gua quente sanit ria...

Page 108: ...Portocaliu Narancs Alaranjado Grey Gri Sz rke Cinza Yellow Galben S rga Amarelo EN ACCESSORIES RO ACCESORII HU TARTOZ KOK EL PT ACESS RIOS BG X6 L N antifreeze heaters L N nc lzitoare antigel L N fagy...

Page 109: ...F S HMV raml sm r V Lv Ventil tor vez rl jel T B T Alacsonyh m rs klet termoszt t A k vetkez k csatlakoztat s hoz T B T alacsony h m rs klet termoszt t v gja kett a TBT felirat feh r jumpert a 2 p lu...

Page 110: ...pira o do ar m m A D C 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 lunghezza tubo scarico fumi m...

Page 111: ...cal vertical f gg leges vertical 6 85 vertical vertical f gg leges vertical 5 85 90 bend 80 125 curba 90 80 125 kanyarulat 90 80 125 90 80 125 curva 90 80 125 90 80 125 80 125 14 12 1 1 5 130 adaptor...

Page 112: ...ez 1 7 8 10 11 12a 12b 13 EL Ac iuni Secven introducerea parolei punctele 1 7 alegerea parametrilor punctele 8 10 modifica i i confirma i parametrul punctele 11 12a iesire fara salvare punctul 12b rev...

Page 113: ...o 60 sec l interfaccia si riposiziona automaticamente sulla schermata principale 13 pressione 2 sec uscita dalla navigazione ritorno a schermata principale 14 modifica range del parametro 11 10 2 sec...

Page 114: ...i intervalul parametrului confirmarea noii valori i revenirea la nivelul anterior reveni i la nivelul anterior f r a salva valoarea presiune 2 sec ie ire din naviga ie reveni i la ecra nul principal D...

Page 115: ...vs Riello Crossover kit DIN vs Riello Riello Filtro magnetico compatto Compact magnetic filter Addolcitore compatto Compact polyphosphate dispenser Kit cantiere con idrometro analogico Building site k...

Page 116: ...7 2 i anexa III din directiva 92 42 CEE Directiva de compatibilitate electromagnetic 2014 30 UE Directiva 2014 35 UE privind echipamentele de joas tensiune Directiva 2009 125 UE privind cerin ele de...

Reviews: