3  CONTROL PANEL (REC10CH)

The REC10CH remote control has the function of a machine interface, displaying the system settings and providing access to the parameters, it also allows the management of functions 

related to the solar system and the heat pump (if present).

The middle of the main screen displays the temperature of the domestic hot water probe, unless there is a heat request in heating mode, in this case the delivery temperature of the 

boiler is displayed. 

The value expressed in bar refers to the system's water pressure.

The top of the screen shows the information regarding the current date and time, as well as the outdoor temperature, if available.

On the left and right sides are displayed the icons indicating the status of the system, their meaning is the following:

The display of the REC10CH control panel is equipped with the new “Color Bar” that rapidly 

informs the user about the boiler operation.

The operating states and the alarms are grouped by 4 colours:

 

-

GREEN

: normal operation, the system is serving domestic hot water/heating requests or 

else automatic functions like, for example, anti-legionella, antifreeze, flue cleaning, etc.. 

Scrolling text describes the function active in that moment

 

-

YELLOW

: presence of faults that could be resolved by the user that allow the product to 

operate even partially. An error triangle on the display gives access to details about the 

fault like, for example, “call for service”, domestic hot water probe fault, etc...

 

-

RED

: presence of lockout faults that require the intervention of the Technical Assistance 

Centre. An error triangle on the display gives access to details about the fault like, for 

example, “stop for service”, lockout, etc...

 

-

GREY

: system is ready to meet any requests or functions, no fault detected.

1.3 

bar

42

°C

MENU

STATE

SET

INFO

HOT WATER TEMPERATURE

FRI

09/04/2021

12:17

PLANT

P

1

2

REC10CH

Boiler control panel

Key area

Confirm

back=  return to the previous screen

 

cancel selection

 

return to the main screen (press > 2 sec.)

-  From the main screen they allow you to choose between the 

options: MENU, INFO, SET, STATE, PLANT.

-  From the sub-menus  they allow you to navigate through the 

different options

This icon indicates that the OFF operating status mode has been set. Each ignition request is ignored except for the anti-freeze function. The pump anti-lock, 3-way valve and anti-

freeze function remain active.
This icon indicates that WINTER mode has been selected (HEATING function enabled). If a heating request from the main zone is in progress, the icon will be flashing.

If there is a CH request from the additional zone, the number 1 or 2 is flashing.

Only if heat pump is present. 

This icon indicates that cooling is active in the SUMMER state. If a cooling request from the main zone is in progress, the icon is flashing. If a 

cooling request from the additional zone is in progress, number 1 is flashing.
This icon indicates that the circuit for domestic hot water production is enabled. When a domestic hot water request is in progress, the icon flashes. The P at the top of the domestic 

hot water icon indicates that the boiler pre-heating function is enabled; the P when flashing indicates that a pre-heating request is in progress.
When the "central heating programming timing" function is enabled this icon indicates that the system heating (main zone) is in AUTOMATIC mode (the management of the heating 

requests follows what has been set with the timer).

If the heating function is not enabled during the current time frame, the icon will be crossed out.
When the "central heating programming timing" function is enabled this icon indicates that the system heating (main zone) is in MANUAL mode (the management of the heating 

requests does not follow what has been set with the programming timing, but it is always active).

OFF

This icon indicates that the main zone, when the “central heating programming timing” function is not enabled, has been set to off (not active).

Only if heat pump is present.

 This icon indicates that the management of a heat pump is enabled. When the heat pump is running, then the icon is flashing.

Only if solar system is present.

 This icon indicates that the management of a solar system is enabled. When the solar system circulator is running, then the icon is flashing.

This icon indicates that the system is detecting the presence of a flame.

This icon indicates the presence of an anomaly, and is always flashing.

 

Only with combined boiler and presence of  heat pump enabled for domestic hot water.

 The icon appears crossed out with an “X” when the system works outside 

the activation times of the heat pump in the domestic hot water, while it flashes when the heat pump is in operation to load the boiler.

Only if photovoltaic enabled.

 When the icon is flashing, it means that the electrical productivity of the photovoltaic system is adequate (closed contact). The system exploits 

the available energy.

This manual describes the operation of the boiler with the REC10CH machine inter-

face.

In case of installation of additional elements (heat pump, boiler, solar, photovoltaic 

system, etc.) it is necessary to refer to the instructions contained in the “Programming 

Manual for the management of hybrid systems”.

If several conditions are present at the same time, the signal on the main screen 

corresponds to the highest priority, in the following ascending order: Grey, Green, Yellow 

and Red.

The configuration MENU is organised with a multi-level tree structure.

An access level has been fixed for each sub-menu: USER level always available; 

TECHNICAL (psw 18)/SERVICE (psw 53) level password protected.

Below is a summary of the MENU tree structure of the REC10CH.

 

b

Some of the information might not be available on the REC10CH depending 

on the access level, the status of the machine or the system configuration

.

Scan the QR CODE to access the Programming Manual for managing 

hybrid systems

Summary of Contents for 20187642

Page 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Page 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Page 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Page 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Page 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Page 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Page 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Page 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Page 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Page 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Page 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Page 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Page 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Page 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Page 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Page 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Page 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Page 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Page 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Page 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Page 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Page 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Page 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Page 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Page 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Page 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Page 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Page 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Page 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Page 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Page 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Page 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...Cod 20187595 09 21 Ed 3...

Reviews: