background image

FAMILY

4

ANTI-FREEZE SYSTEM

The boiler is fitted as standard with an automatic anti-freeze system that activates when the 

temperature of the water in the primary circuit falls below 5°C. This system is always active 

and provides protection for the boiler up to an air temperature in the installation area of >0°C. 

 

b

To take advantage of this protection (based on burner operation), the boiler 

must be able to switch itself on; any lockout condition (for ex. due to a lack 

of gas or electrical supply, or the intervention of a safety device) therefore 

deactivates the protection.

 

b

When the boiler is installed in a place where there is a risk of freezing, with 

outside air temperatures below >0 °C, an antifreeze heater kit must be used 

to protect the DHW circuit and condensation drain (available on request - see 

catalog) that protects the boiler up to -15 °C.

 

b

The installation of the antifreeze heater kit must be carried out only by 

authorized personnel, following the instructions contained in the kit.

In normal operating conditions, the boiler can protect itself against frost.

 

You are advised 

to add a good quality anti-freeze liquid to the primary circuit (respecting the manufacturer’s 

indications) if the temperature falls below >0°C, with the electricity supply disconnected and 

the heating system full. For the hot domestic water part, we recommend you drain the circuit.

The boiler component materials are resistant to ethylene glycol based antifreeze liquids.

MINIMUM DISTANCES

To ensure access to the boiler for normal maintenance operations, respect the minimum 

installation clearances envisaged.For correct appliance positioning, bear in mind that:

 

-

it must be installed on a wall that can support its weight

 

-

it must not be placed above a cooker or other cooking device

 

-

it is forbidden to leave inflammable products in the room where the boiler is installed

 

-

heat-sensitive walls (e.g. wooden walls) must be protected with proper insulation.

*

* see paragraph 2.7

measured in mm

2.3 

Instruction for condensation exhaust connection

This product is designed to prevent the escape of gaseous products of combustion through 

the condensation drain pipe with which it is equipped, this is obtained by using a special 

siphon placed inside the appliance. 

 

b

All components of the product condensation drain system must be properly 

maintained in accordance with the manufacturer instructions and cannot be 

modified in any way.

The condensation exhaust system downstream of the appliance must comply with the 

relevant legislation and standards. The construction of the condensation exhaust system 

downstream of the appliance is the responsibility of the installer. The condensation 

exhaust system must be dimensioned and installed in such a way as to guarantee the 

correct evacuation of the condensation produced by the appliance and/or collected by 

the evacuation systems of combustion products. All the components of the condensation 

exhaust system must be made in a workmanlike manner using materials that are suitable for 

withstanding the mechanical, thermal and chemical stresses of the condensation produced 

by the appliance over time. 

Note:

 If the condensation exhaust system is exposed to the risk 

of frost, always provide an adequate level of insulation of the pipe and consider any increase 

in the diameter of the pipe itself. The condensation exhaust pipe must always have an 

adequate slope level to prevent the condensation from stagnating and its proper drainage.

The condensation exhaust system must have an inspectable disconnection between the 

condensation exhaust pipe of the appliance and the condensation exhaust system.

2.4 

Electrical wiring

Low voltage connections

Carry out the low voltage connections as follows:

 

-

use connectors supplied as standard:

 

-

4-poles ModBus connector for BUS 485 (- A B +)

 

-

8--poles connector for TBT - TA - OT+ - SE

CE4

(- A B +)

Bus 485

CE8

TBT

Low temperature limit thermostat

TA

Room thermostat (contact without voltage)

OT+

Open therm

SE

Outdoor temperature sensor

bianco

white

nero

black

- A B +

TBT

TA OT+

SE

bianco

nero

Utilizzare contatto 

privo di tensione

CE4

CE8

Voltage free 

contact input

 

-

carry out the electrical wiring connections using the desired connector as shown in the 

detailed drawing

 

-

once the electrical wiring connections have been made, correctly insert the connector 

into its counterpart.

 

b

We recommend using conductors with a section no larger than 0,5 mm2.

 

b

In the event of TA or TBT connection, remove the related jumpers on the terminal board.

OTBus

 remote control connection

When an OTBus remote control is connected to the system, the boiler display shows the 

message “Open Therm Connected”, while some of its functions are disabled and transferred 

to the OTBus remote control that takes control of the domestic hot water and heating 

functions regarding the main zone.

42

°C

MENU

STATE

SET

INFO

OPENTHERM CONNECTED

HOT WATER TEMPERATURE

FRI

1.5 

bar

09/04/2021

12:17  

PLANT

In particular on the boiler display:

 

-

it is no longer possible to set the boiler OFF/WINTER/SUMMER status (it is set by the 

OTBus remote control)

 

-

it is no longer possible to set the domestic hot water setpoint (it is set by the OTBus 

remote control)

 

-

it is not possible to activate the CHIMNEY SWEEPER function if a OTBus remote control 

is connected to the boiler.

In addition

 

-

The domestic hot water setpoint is displayed in the INFO menu in the place of the flow 

meter flow rate value.

 

-

The heating setpoint set on the boiler display is used only if there are heat requests from 

the TA and the OTBus remote control does not have a request if the parameter DO_AUX1 

= 1 or DO_AUX1 = 0 and the jumper on 1-2 pin of X21 is closed. We should point out that 

it is not possible, with the OTBus remote control connected, to change the values of the 

parameters ACTUATION TYPE and REQUEST TYPE of the main zone.

 

b

The OpenTherm connection is not enabled in the presence of a heat pump.

Note: an OT+ remote control cannot be connected if the system already has a 

REC10CH or BE16 interface boards. in this case the system gives the following error 

message:

WRONG CONFIGURATION 

OPENTHERM CONNECTED

High voltage connections

The connection to the mains supply must be made via a separation device with an omnipolar 

opening of at least 3.5 mm (EN 60335/1 - category 3). The appliance works with alternating 

current at 230 Volt/50 Hz, and is in compliance with Standard EN 60335-1. It is obligatory to 

make the connection with a safe ground/earth, in compliance with current directives.

 

b

The  installer is responsible for ensuring the appliance is suitably earthed;  the 

manufacturer will not be liable for any damage resulting from an incorrect or absent 

earth connection.

 

b

It is also advisable to respect the phase-neutral connection (L-N).

Summary of Contents for 20187642

Page 1: ...Family KIS EN INSTALLER AND USER MANUAL...

Page 2: ...ser also Warning This instructions manual contains data and information for both the user and the installer Specifically note that the user for the use of the appliance must refer to chapters Warnings...

Page 3: ...this case ventilate the room by opening the doors and windows close the fuel shut off device ask the Technical Assistance Service or professionally qualified personnel to intervene promptly a It is f...

Page 4: ...pe and consider any increase in the diameter of the pipe itself The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper draina...

Page 5: ...and immediately before and after each change of direction curve b The boiler is supplied without the flue gas exhaust air suction kit since it is possible to use the accessories for condensing applia...

Page 6: ...e can exceed the static pressure of the collective air duct of 25 Pa in the condition in which n 1 boilers work at maximum rated heat input and 1 boiler at the minimum rated heat input allowed by the...

Page 7: ...e vent cycle Remove any air in the domestic system radiators zone manifolds etc using the bleed valves Once again check that the system pressure is correct ideally 1 1 5 bar and restore the levels if...

Page 8: ...is in progress number 1 is flashing This icon indicates that the circuit for domestic hot water production is enabled When a domestic hot water request is in progress the icon flashes The P at the to...

Page 9: ...LER CHANGE NAME INSTALLER PI PROPORTIONAL 5 0 99 SERVICE only mixing zones with ACTUATION BE16 PI INTEGRAL 10 0 99 SERVICE only mixing zones with ACTUATION BE16 VALVE RUN 120 sec 0 sec 120 sec SERVICE...

Page 10: ...request type TA and zone type HT 0 4 0 2 0 8 INSTALLER if EXTERNAL PROBE request type TA and zone type LT 2 0 1 0 5 0 INSTALLER if request type AMBIENT PROBE or REC10CH AMBIENT INFLUENCE 10 0 20 INSTA...

Page 11: ...DISABLE COOLING FUNCTION NOT ACTIVE FUNCTION ACTIVE FUNCTION NOT ACTIVE INSTALLER USE FOR DHW DON TUSE FOR DHW DHW FUNCTION NOT ACTIVE DHW FUNCTION ACTIVE DHW FUNCTION NOT ACTIVE INSTALLER if BE17 pre...

Page 12: ...t it has all the safety and control devices required by current regulations that the circulator rotates freely because especially after long periods of inactivity deposits and or debris can prevent fr...

Page 13: ...ZONE PARAMETERS WEATHER COMPENSATION INSTALLATION RANGE RATED CALIBRATION INSTALLER TECHNICAL SENSOR CALIBRATION ZONES MANAGER SYSTEM RESET INSTALLER INSTALLATION ADD ZONE MODIFY ZONE DELETE ZONE INS...

Page 14: ...URE C EXTERNAL TEMPERATURE C NIGHT COMPENSATION If a timer is connected to the ROOM THERMOSTAT input the NIGHT COMP function can be enabled as follows menu TECHNICAL WEATHER COMPENSATION CLIMATIC CURV...

Page 15: ...in standby again keeping the outlet temperature displayed If faults arise in ignition or operations the boiler performs a SAFETY STOP the triangle signalling faults will flash on the REC10CH To identi...

Page 16: ...Technical Assistance Centre 4 13 Gas conversion Conversion from a family gas to other family gas can be performed easily also when the boiler is installed This operation must be carried out by profes...

Page 17: ...l E042 water pressure transducer fault definitive E060 domestic hot water probe fault transitional E070 flow sensor faulty flow sensor overtemperature flow return sensor differential alarm transitiona...

Page 18: ...TECHNICAL Note After a reset it is necessary to carry out a new configuration of the system for details about this procedure see the following section 4 19 System configuration b This operation must b...

Page 19: ...in intact and to comply with prescriptions of current regulations it is necessary to render the appliance to systematic checks at regular intervals When carrying out maintenance work observe the instr...

Page 20: ...nnect the tubes A and B remove the clip C and remove the siphon Unscrew the bottom and top caps then remove the float Clean the parts of the siphon from any solid residues b Do not remove the safety s...

Page 21: ...EFAULT VALUE FACTORY SET MINIMUM VALUE MAXIMUM VALUE ACCESS LEVEL NOTES MENU SETTINGS USER TIME DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ITALIA...

Page 22: ...ed programme 8 2 3 MANUAL If MANUAL is selected the zone requests will be managed based on the setpoint set by the user 8 2 4 HEAT OFF If HEAT OFF is selected the zone requests will not be fulfilled N...

Page 23: ...0 INFO The INFO function can be used to display a series of data regarding the system ATTENTION The displayed data cannot be modified SCREED HEATER OPERATING HOURS DELIVERY PROBE RETURN PROBE DOMESTIC...

Page 24: ...TART THURSDAY USE THE ARROWS TO MODIFY ENTER START TIME ADD PERIOD END MAIN Once the operation completed the display will show 07 30 08 30 11 30 14 00 13 30 15 00 18 00 22 30 START THURSDAY ADD MODIFY...

Page 25: ...TURE WILL BE ADJUSTED WITH NEW TARGET SET POINT UNTIL 09 04 2021 ON 13 15 1 ZONE1 CONFIRM CANCEL 00 30 YOU ARE ACTIVATING COMFORT MODE ENTER TIME DURATION IN HOURS USE THE ARROWS TO MODIFY 1 ZONE1 26...

Page 26: ...Maximum pressure bar 8 8 8 Minimum pressure bar 0 15 0 15 0 15 Quantity of hot water with t 25 C 30 C 35 C l min 15 1 12 5 10 8 18 1 15 1 12 9 20 8 17 4 14 9 DHW minimum capacity l min 2 2 2 Selectio...

Page 27: ...ith reference to Delegated Regulation EU No 811 2013 the data in the table can be used for completing the product card and the labelling for ambient heating appliances for mixed heating appliances for...

Page 28: ...ivery 34 Hot water 35 Gas 36 Heating return 37 Cold water 2 21 AF AC M R 20 19 1 6 6 8 9 5 4 6 7 3 2 18 15 14 13 12 11 10 16 17 15 3 Residual head of circulator Fig 3 A B C Residual head mbar Flow rat...

Page 29: ...entering a value 10 the circulator speed will change to achieve a system flow rate with the aim of maintain ing the T of 10 C upstream and down stream of the exchanger 3 CIRCULATOR IN MAXIMUM FIXED S...

Page 30: ...Wiring diagram Blu Blue Marrone Brown Nero Black Rosso Red Bianco White Viola Violet Rosa Pink Arancione Orange Grigio Grey Giallo Yellow Verde Green A Gas valve B 230V auxiliary C Voltage free contac...

Page 31: ...from 60 100 to 80 80 110 65 65 1 1 5 90 bend 60 100 60 100 horizontal 10 horizontal 6 horizontal 6 1 3 1 6 105 vertical 11 vertical 7 vertical 7 90 bend 80 125 80 125 25 15 15 1 1 5 130 adaptor from 6...

Page 32: ...T OPTION 4 and SYSTEM INFO INSTALLATION WEATHER COMPENSATION RANGE RATED TECHNICAL INSTALLER 5 PARAMETERS CALIBRATION and ANTI CYCLE FUNCTION RESET CH TIMERS DHW THERMOSTAT PARAMETERS INSTALLER 6 PUMP...

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ...Cod 20187595 09 21 Ed 3...

Reviews: