The cable sections specified in the table are minimum re-
quirements. The correct size must be calculated taking in-
to account the actual length, the type of routing and other
conditions set by the existing regulations.
—
fasten the wires with the wire retainer
—
complete the electric connections and refit all components
by performing the described operations in reverse order
MODEL 35
1
Terminal board cover panel
2
Connection power cable
3
Liquid pipe
4
Gas pipe
5
Connections cover
1
2
3
4
5
Check that:
—
the characteristics of the power network are suitable for
the device usage values
—
the power supply voltage corresponds to the nominal va-
lue +/- 10%, with a maximum phase imbalance of 3%
—
all of the power network disconnect devices must be
equipped with contact openings (3 mm) in order to allow
for complete disconnection, in accordance with the con-
ditions required
Mandatory items:
—
have an omnipolar magneto-thermal circuit breaker and
a padlockable disconnecting switch compliant with the
IEC-EN Standards (contact opening of at least 3 mm), with
adequate breaking power and differential protection, in-
stalled near the equipment
—
connect the device to a properly functioning earthing sy-
stem
—
make sure that the electrical power supply system is com-
pliant with the current national safety standards
—
make sure that the power supply line impedance is consi-
stent with the unit's power consumption, as indicated on
the unit's data plate
—
for any electrical intervention, always refer to the wiring
diagrams contained within this booklet
—
take anti-static precautions in case of weather conditions
where humidity is less than 40%
9
Electric connections shall be made in compliance with na-
tional regulations.
9
Avoid placing the connection cables less than 1 metre away
from radio and video systems.
9
Avoid using mobile phones.
0
It is forbidden to earth the device together with pipes, li-
ghtning conductors or the earthing system of a telephone
line. Using an improper earthing system can cause electric
shocks.
0
It is forbidden to connect other devices in parallel to the
unit.